THERE ARE 3 SWITCHES TO SET WITH LIMITS:

CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS

THERE ARE 3 SWITCHES TO SET WITH LIMITS:

1)Switch 1: Sets the limit to trip either above or below the Limit Value.

2)Switch 2: Sets whether Relay 1 will trip when the condition occurs.

3)Switch 3: Sets whether Relay 2 will trip when the condition occurs.

After the switches are set, the limit value should be programmed (see table in section 12.4).

LM1

LM2

SWITCH 1

SWITCH 2

SWITCH 3

VALUE

LED

LED

ABOVE/BELOW

RELAY 1

RELAY 2

 

ON

OFF

Digit Up-trigger above value

Digit Up-enabled

Digit Up-enabled

0-9999

 

 

Digit Down-trigger below

Digit Down-

Digit Down-

0-9999

 

 

value

disabled

disabled

 

OFF

ON

Digit Up-trigger above value

Digit Up-enabled

Digit Up-enabled

0-9999

 

 

Digit Down-trigger below

Digit Down-

Digit Down-

0-9999

 

 

value

disabled

disabled

 

Table 12.5: Group 5: Functions 0–7

LM1

LM2

SWITCH 1

SWITCH 2

SWITCH 3

VALUE

ON

OFF

Digit Up

Digit Up

Digit Down

0120

OFF

ON

Digit Down

Digit Down

Digit Up

0090

Table 12.6: Group 5: Example for Function 0

Thus, if Kilowatts exceed 120 W, LM1 is triggered and Relay 1 is tripped.

If the Kilowatts fall below 90 W, LM2 is triggered and Relay 2 is tripped.

SPECIAL CASES

FREQUENCY: FUNCTION 4 contains a permanent decimal after the second digit. The highest and lowest level limits that can be programmed are 99.99 and 00.00, respectively.

POWER FACTOR: FUNCTIONS 3 and 6 contain a permanent decimal after the first digit. The highest and lowest limits that can be programmed are 1.000 and 0.000, respectively.

74

EPM 5000 series Advanced Power Meters

GE Multilin

Page 78
Image 78