GE EPM 5200, EPM 5300, EPM 5350 instruction manual Voltage Range, Input Source, GROUP 2 VALUE

Models: EPM 5300 EPM 5200 EPM 5350

1 100
Download 100 pages 46.61 Kb
Page 72
Image 72
VOLTAGE RANGE

CHAPTER 11: PROGRAMMING GROUP 2 – METER CALIBRATION

VOLTAGE RANGE

INPUT SOURCE

GROUP 2 VALUE

69.3/120V

75V

1440

120/208V

120V L-N

1440

277/480V

300V

0300

5A CT High End

5A

2000

2.5A Low End

2.5A

1000

Table 11-2: Calibration Source, Full Scale and Value Settings for Calibration

11.2: Group 2, Functions 0–2—High End Calibration of Voltage Channels, High and Low End Calibration of Amperage Channels

To change the calibration (high end—Functions 0 and 1):

NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

 

MAX

 

 

 

 

 

 

 

AC VOLTS

 

 

MAX

 

 

 

 

 

 

 

 

 

 

 

 

 

AC VOLTS

 

 

 

 

 

 

 

 

A B C A B C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B C A B C

 

MIN

 

 

 

 

 

 

 

N N N B C A

 

 

MIN

 

 

 

 

 

 

 

 

 

 

 

 

 

N N N B C A

 

LM1

 

 

 

 

 

 

 

 

 

LM1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LM2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LM2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC AMPS

 

 

 

 

 

 

 

 

 

 

 

A B C N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B C N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA

 

 

KVAH

 

 

KWH

 

FREQ

 

 

 

 

 

KVAR

 

 

 

KVAH

 

KWH

 

FREQ

 

 

 

KVAR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX/MIN

POWER PHASE

LIMITS VOLTS AMPS

NEXT

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 2. appears in upper display.

c. Press AMPS to activate the Group.

!A one-digit password is required to continue.

d.Press VOLTS until 5 appears.

e.Press AMPS to select.

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 2:

!Refer to Table 11-1for Function Number that corresponds to the area requiring calibration. Calibration for each area begins with A and then moves to B and C.

a. Press MAX/MIN/LIMITS to change Function number.

68

EPM 5000 series Advanced Power Meters

GE Multilin

Page 72
Image 72
GE EPM 5200, EPM 5300, EPM 5350 instruction manual Voltage Range, Input Source, GROUP 2 VALUE