CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

 

MAX

 

 

 

 

 

 

 

 

 

 

 

 

AC VOLTS

 

 

 

 

 

 

 

 

 

 

 

 

 

A B C A B C

 

MIN

 

 

 

 

 

 

 

 

 

 

 

 

N N N B C A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LM1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LM2

 

 

 

 

 

 

 

 

 

 

 

 

AC AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B C N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA

 

 

KVAH

 

KWH

 

FREQ

 

 

 

KVAR

 

 

 

 

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 3:

a. Press AMPS once to begin Data Entry Sequence.

!The previous value shifts to middle display and four dashes appear in lower display.

b. Press VOLTS for desired number.

c. Press AMPS to store each digit.

 

MAX

 

 

 

 

 

 

 

 

 

 

 

AC VOLTS

 

 

 

 

 

 

 

 

 

 

 

 

A B C A B C

 

MIN

 

 

 

 

 

 

 

 

 

 

 

N N N B C A

 

 

 

 

 

 

 

 

 

 

 

 

 

LM1

 

 

 

 

 

 

 

 

 

 

 

 

LM2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B C N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA

 

 

KVAH

 

 

KWH

 

FREQ

 

 

 

KVAR

 

 

 

 

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

!Repeat this procedure until new Address is entered.

!When complete, middle display blanks and lower display indicates new Address.

See Chapter 14 to Exit.

9.3: Group 0, Function 2—BAUD RATE

BAUD RATE: Speed at which data is transmitted between meter and remote computer or serial printer. The rate programmed into the meter must match the rate used by the remote device. Valid Baud Rates are 1200, 2400, 4800 and 9600.

To change the Baud Rate:

NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 0. appears.

c. Press AMPS to activate the Group.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

PF

KW

KVA

KVAH

 

KWH

 

FREQ

 

KVAR

 

 

 

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 2:

a. Press MAX/MIN/LIMITS until Function 02. appears in upper display.

!Lower display indicates current Baud Rate.

GE Multilin

EPM 5000 series Advanced Power Meters

45

Page 49
Image 49
GE EPM 5300, EPM 5200, EPM 5350 instruction manual Group 0, Function 2-BAUD Rate