9.9: Group 0, Function 6—KYZ Parameter Selection

CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

9.9: Group 0, Function 6—KYZ Parameter Selection

NOTE: FUNCTION 6 applies only if Option -NL or -NL2 was ordered.

OPTION -NL: This option gives the meter 2 Relays and one KYZ pulse. The KYZ pulse can be programmed to the below features.

Select a single parameter from Table 9-5according to the EPM 5300P model being programmed.

OPTION -NL2: This option offers 3 distinct KYZ pulses instead of Relays.

Only three separate parameters may be selected: FUNCTION 6.0 (KYZ Port 0), FUNCTION 6.1 (KYZ Port 1), and FUNCTION 6.2 (KYZ Port 2). The available parameters vary according to the EPM 5300P model being programmed. For exact port positions see Installation Sections.

PARAMETER

DESCRIPTION

0

Disable KYZ

1

Positive Watt Hour KYZ

2

VA Hour KYZ

3

Negative Watt Hour KYZ

4

Positive VAR Hour KYZ

5

Negative VAR Hour KYZ

Table 9-5: KYZ Parameters

APPLICABLE SELECTIONS: 5300P - +WH, -WH, VAH

5300P+R* - +WH, -WH, +VARH, -VARH

*(-R option gives the 5300P VAR/Hour readings instead or VA/Hours). To perform the KYZ Parameter Selection:

NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

NOTE: FUNCTION 6 applies only if Option -NL or -NL2 was ordered.PARAMETER PF

Manual backgroundManual background KW

Manual backgroundManual background KVA

KVAH

 

KWH

 

FREQ

 

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

NEXT

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 0. appears in upper display.

c. Press AMPS to activate the Group.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

Manual backgroundManual background PF

Manual backgroundManual background KW

Manual backgroundManual background KVA

KVAH

 

KWH

 

FREQ

 

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

NEXT

Step 2:

a. Press MAX/MIN/LIMITS until 06.P appears in upper display.

(Standard Selection is 1).