PROGRAMMING STEPS:

CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

PROGRAMMING STEPS:

1.Enter in GROUP 0, FUNCTION 4, PACK ‘P’, Segment C and D: UP, UP.

2.Enter in GROUP 5, FUNCTION 4, LIMIT 1, Segments B, C, and D: DOWN, UP, DOWN. Value: 58.00.

3.Enter in GROUP 5, FUNCTION 4, LIMIT 2, Segments B, C, and D: UP, UP, DOWN. Value: 62.00.

Example 2: Normally reset—non-event condition is reset relay

Relay 1 will be “SET” if the instantaneous reading for amps is below 4.00 or above 5.00 amps. Under all other conditions the relay will be “RESET”.

NOTE: Under this setup the relay will NOT act as a protective switch.

 

S E T

L M 1

5 . 0 0

A

 

R E S E T

 

4 . 0 0

A

L M 2

 

S E T

 

0 . 0 0

A

R E S E T

 

N O P O W E R T O T H E U N I T

PROGRAMMING STEPS:

1.Enter in GROUP 0, FUNCTION 4, PACK ‘p’, Segments C and D: DOWN, DOWN

2.Enter in GROUP 4, FUNCTION 2, LIMIT 1, Segments: B, C, and D: UP, UP, DOWN. Value: 5.00

3.Enter in GROUP 4, FUNCTION 2, LIMIT 2, Segments: DOWN, UP, DOWN. Value: 4.00

GROUP 0—FUNCTION NUMBER

DESCRIPTION

04.P
Controls Relay 1
05.P
Controls Relay 2 (and 3 if NL4)

Relay Mode: Group 0, Functions 4–5