HOW TO USE KYZ PULSE VALUE TABLE FOR MULTIPLICATION:

CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

HOW TO USE KYZ PULSE VALUE TABLE FOR MULTIPLICATION:

SITUATION 1: FSW=9999.

SITUATION 2: FSW=999.9

Selection is Multiply by 2

Selection is Multiply by 2

This means that every .5 unit WH =1 pulse.

This means that every .05 unit WH=1 pulse.

Unit=Kilo (see Group 1, Function 2)

Unit=Kilo (see Group 1, Function 2)

Result: For every 1 KWH increment on the

Result: For every 1 KWH increment on the

counter, the meter will output 2 pulses.

counter, the meter will output 20 pulses.

SITUATION 3: FSW=99.99

Selection is Multiply by 20

This means that every .0005 unit WH=1 pulse.

Unit=Kilo (see Group 1, Function 2)

Result: For every 1 KWH increment on the counter, the meter will output 2,000 pulses.

SITUATION 4: FSW=9.999

Selection is Multiply by 20

Unit=Kilo (see Group 1, Function 2)

This means that every .00005 WH=1 pulse.

Result: For every 1 KWH increment on the counter, the meter will output 20,000 pulses.

HOW TO USE THE KYZ PULSE VALUE TABLE FOR DIVISION:

SITUATION 1: FSW=9999.

SITUATION 2: FSW=999.9

Selection is Divide by 10

Selection is Divide by 10

This means that every 10 unit WH=1 pulse.

This means that every 1 unit WH=1 pulse.

Unit=Kilo (see Group 1, Function 2)

Unit=Kilo (see Group 1, Function 2)

Result: For every 10 KWH increment on the

Result: For every 1 KWH increment on the

counter, the meter will output 1 pulse.

counter, the meter will output 1 pulse.

SITUATION 3: FSW=99.99

Selection is Divide by 20

This means that every .2 unit WH=1 pulse.

Unit=Kilo (see Group 1, Function 2)

Result: For every 1 KWH increment on the counter, the meter will output 5 pulses.

To change the KYZ pulse value:

SITUATION 4: FSW=9.999

Selection is Divide by 20

Unit=Kilo (see Group 1, Function 2)

This means that every .02 WH=1 pulse.

Result: For every 1 KWH increment on the counter, the meter will output 50 pulses.

MAX

AC VOLTS

A B C A B

C

MIN

N N N B C A

LM1

 

 

LM2

AC AMPS

 

 

 

 

A B C N

 

 

POWER

SITUATION 1: FSW=9999.SITUATION 2: FSW=999.9 PF

SITUATION 3: FSW=99.99SITUATION 4: FSW=9.999 KW

HOW TO USE THE KYZ PULSE VALUE TABLE FOR DIVISION:Manual background KVA

KVAH

 

KWH

 

FREQ

 

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

MAX

AC VOLTS

A B C A B

C

MIN

N N N B C A

LM1

 

 

LM2

AC AMPS

 

 

 

 

A B C N

 

 

POWER

 

 

 

PF

 

 

 

KW

 

 

 

KVA

KVAH

KWH

FREQ

KVAR

MAX/MIN

VOLTS AMPS

POWER

PHASE

LIMITS

NEXT

 

MAX

 

 

 

 

 

 

 

 

 

 

 

AC VOLTS

 

MIN

 

 

 

 

 

 

 

 

 

 

 

A B C A B C

 

 

 

 

 

 

 

 

 

 

 

 

N N N B C A

 

LM1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LM2

 

 

 

 

 

 

 

 

 

 

 

AC AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B C N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVAH

 

 

KWH

 

 

 

FREQ

 

 

 

 

 

KVAR

 

 

 

 

 

 

 

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 1:

a. Enter Group Level of Programming Mode, (see Chp. 8).

b. Press MAX/MIN/LIMITS until 0. appears in upper display.

c. Press AMPS to activate the Group.

Step 2:

Step 3:

a. Press MAX/MIN/LIMITS until 06.P

a. Press AMPS to change current

appears in upper display.

setting.

! The lower display indicates

! The decimal point next to the 6

multiplication or division factor.

disappears.

 

b. Press MAX/MIN/LIMITS to

 

advance selections. -or-

 

c. Press VOLTS to reverse.

 

(Until desired factor appears).

!Division is indicated by div appearing in the middle display.

When middle display is blank, it indicates multiplication.

d. Press AMPS to store.