CHAPTER 12: GROUPS 4, 5, AND 6 – SET LIMITS AND RELAYS

12.5: Group 6, Functions 0–5—LM1/LM2 Set Limits and Relay Triggers for Over/Under %THD Conditions

LM1 LED

LM2 LED

SWITCH 1

SWITCH 2

SWITCH 3

LEVEL

 

 

ABOVE/BELOW

RELAY 1

RELAY 2

 

ON

OFF

Digit Up

Digit Up

Digit Down

012.0

OFF

ON

Digit Down

Digit Down

Digit Up

009.0

Table 12.9: Group 6—Example for Function 0

So, if THD exceeds 12%, LM1 is triggered and Relay 1 is enabled.

If THD falls below 9%, LM2 is triggered and Relay 2 is enabled.

12.6: Limits or Relays Programming Procedure

NOTE: The procedure for programming any limit or relay for each group is identical. The example below signifies the exact procedure for programming a Limit/Relay for GROUPS 4–6.

—Group 4 is used as an example.

NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

GROUP

 

AC VOLTS

 

MIN

A B C A B C

 

N N N B C A

 

LM1

 

 

 

LM2

AC AMPS

 

 

 

 

A B C N

 

 

POWER

 

 

 

PF

 

 

 

KW

 

 

 

KVA

KVAH

KWH

FREQ

KVAR

MAX/MIN

VOLTS AMPS

POWER

PHASE

LIMITS

 

NEXT

LIMIT VALUE

MAX

AC

C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

POWER

LM2 LEDLEVEL PF

12.6: Limits or Relays Programming ProcedureManual background KW

Manual backgroundManual background KVA

KVAH

 

KWH

 

FREQ

 

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

FUNCTION

RELAY SWITCHES

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 4. appears in upper display.

c. Press AMPS to activate the Group.

Step 2:

a. Press MAX/MIN/LIMITS to select desired Function.

!Middle display provides the currently selected value for whether to trip above or below, activate Relay 1 and activate Relay 2.

Left Switch: UP position indicates above tripping value for lower display’s value. DOWN position indicates below tripping.

Middle Switch: UP position sets Relay 1 to trip.

DOWN position doesn’t activate Relay 1 when limit condition exists.

Right Switch: Same as Middle Switch , regarding Relay 2.

b. Press VOLTS to toggle between LM1 and LM2 settings.

!The LM1 or LM2 annunciator indicates the limit being displayed.

76

EPM 5000 series Advanced Power Meters

GE Multilin