I/O Limits

Select System again. From the configuration menu, select ConfigLimits (click the mouse on that line or cursor down and press Enter).

'

Entries made on this screen determine how the GMR software allocates memory. The maximum number of groups that can be configured is 128. Additional parameter limits for this screen are summarized below.

Item

Parameters

Comment

 

 

 

Totalnumber of voted digital inputs

1...112 (788 CPU)

In increments of 16 or 32

and redundant outputs

1...2048(789CPU)

 

Number of voted analog inputs

1...1024

In increments of 4 or 6

 

 

 

%AI Analog Input Table size

1...8192

 

 

 

 

%R register table size

1 to 16

Specified in increments of 1K

Voted Discrete

Enter the number of 16-circuit and 32-circuit discrete input and output groups in the system (plus any spare groups you may add in the future). Each input group may consist of 1, 2, or 3 blocks. The GMR software will assign these voted I/O addresses at the beginning of the I/O tables, and ªrawº data addresses at the end of the I/O tables (similar to the illustration of analog inputs, below, and discussed in detail in chapter 7).

Analog

Enter the number of groups made up of 6-input analog blocks and the

In Groups

number of groups made up of 4-input (2-output) blocks. Include any

 

spare groups you may add in the future

Tables

Enter the amounts of word memory to be allocated to analog input data

 

(%AI) and register data (%R). These values must match the

 

corresponding values configured using Logicmaster 90.

 

%AI Size: Allow enough %AI memory to accommodate all analog input

 

data, as explained below. The maximum size is 8192 analog channels (words).

 

%AI memory is divided into sections:

Input

Voting

Logic

Ainputs

Binputs

Cinputs

%AI0001

A

B

C

Voted Inputs

non-voted Inputs