GMR Status and Control (%M) References

The GMR system software uses several %M references as status or control bits. Status bits are used by the GMR software to provide information about GMR operations. These references can be read as needed by the application program. The control bits can be used by the application program to provide information to the GMR software.

%M Status References

The following table lists the GMR system status flags.

Reference

Nickname

Name

Meaning

 

 

 

 

%M12225

PLCA

PLC Ident is A

This is PLC A (all GMR bus controllers =31). For

 

 

 

references %M12225, 26, and 27, only one will be

 

 

 

set in each PLC.

%M12226

PLCB

PLC Ident is B

This is PLC A (all GMR bus controllers =30).

%M12227

PLCC

PLC Ident is C

This is PLC A (all GMR bus controllers =29).

%M12228

PLCAOK

PLC A is online

Meaning depends on the PLC where the flag is

 

 

 

set. See the table on the next page.

%M12229

PLCBOK

PLC B is online

º

%M12230

PLCCOK

PLC C is online

º

%M12231

INHIBIT

Inhibituserapplication

Set by the GMR software at startup, to prevent

 

 

 

execution of the application program until data

 

 

 

initializationiscomplete.

%M12232

MISCMP#*

Init.miscompareat

InitializingPLCdetectsmiscomparebetween

 

 

startup

%M (bit) init. data from two online PLCs.

%M12234

SYSFLT#*

System fault at startup

At startup, communications failure with a GMR

 

 

 

buscontroller.

%M12235

SYSFLT

Systemfault

Communications failure with a GMR bus con-

 

 

 

troller. This reference is cleared when PLC Fault

 

 

 

Reset is issued.

%M12236

OPDISC

O/Pdiscrepancy

Outputdiscrepancy. This reference is cleared

 

 

 

when PLC Fault Reset is issued.

%M12237

COLDST*

Cold start performed

At startup, the initializing PLC detects no other

 

 

 

PLCs online. When the application program

 

 

 

detects this flag has been set, it can initialize any

 

 

 

%M and %R initialization data.

%M12238

IORESIP

I/Oresetinprogress

An I/O fault reset is in progress. Bit is On for one

 

 

 

scan when the internal GMR fault tables are

 

 

 

cleared.

%M12239

ATINPRG

Autotest in progress

An input or output autotest is in progress (not

 

 

 

necessarily initiated by this PLC) the state of this

 

 

 

bit will be the same in all runningPLCs.

%M12240

LOGONFT

Block logon fault

See page 7-17.

%M12241

SIMPLEX

Simplex mode

One PLC controls the system. •

%M12242

DUPLEX

Duplex mode

Two PLCs control the system. •

 

 

 

 

%M12243

TRIPLEX

Triplex mode

Three PLCs control the system. •

 

 

 

 

%M12244

IO_SD

AnyI/OShutdown

At least one of the PLCs has begun timing an I/O

 

 

Timeractivated

Shutdown.

%M12245 through %M12256, %M12233

Reserved for future GMR use.

*Will only be set at startup if condition occurs. D Only one of these three will be set at a time.