8

Input Wiring (continued)

Block Wiring for 32-Circuit Sink Block in an Input Group

DC Sink Block IC660BBD025

If single sensor, it must also be

 

wired to corresponding point on

 

two other input blocks

 

22V to 30V DC

S1

S2

Genius Bus

 

Connections

SHLD IN

 

 

SHLD OUT

 

+5V

 

DC+

 

DC+

 

DC+

Device #1

DC+

10

 

12

Required at each input (for Input

14

Autotesting). 1N5400 or equivalent.

16

 

 

18

 

20

 

22

Output 16

24

 

26

If group inputs are configured for autotesting, circuit 16 must be used as an output

28

 

If no autotesting is to be done on this group of inputs, the input devices must not be wired to

30

circuit 16. They must be wired to the power source instead.

32

If group uses single sensors, point 16 must also be wired to corresponding point on two

34

other input blocks

36

Zener diode required at each powerfeed output (for Input Autotesting). 1N5400 or equivalent.

38

 

 

40

 

42 DC±

Device #32

DC±

44 DC±

 

 

DC±

 

46 DC±

OVDC

 

Connection if no points on the

Ground

block are to be autotested

 

(must disconnect output 16).

 

HIn three-block input group, each block is connected to one bus of three.

HIf redundant power supplies are to be used, they should be diode ªORedº power supplies providing common power to all blocks in a group. Different groups may use different power sources.

GFK-0787B

Chapter 8 Installation Information

8-9

Page 190
Image 190
GE GFK-0787B user manual Block Wiring for 32-Circuit Sink Block in an Input Group, DC Sink Block IC660BBD025