Results of Block Voting with Only Two PLCs Online

In the two tables below, PLC C is shown as offline, but it could be either of the other two instead.

Using 0 as the Duplex Default state means that when only two PLCs are online, the voted output state will be 0 if either PLC sets it to 0. It will not be 1 unless both online PLCs set it to 1.

PLC A

PLC B

PLC C

Duplex

Voted

Output

Output

Output

Default

Output

State

State

State

Setting in

State

 

 

 

Block

 

 

 

 

 

 

0

0

±

0

0

 

 

 

 

 

0

1

±

0

0

 

 

 

 

 

1

0

±

0

0

 

 

 

 

 

1

1

±

0

1

 

 

 

 

 

Similarly, using 1 as the Duplex Default state means that when only two

PLCs are online, the voted output state will be 1 if either PLC sets it to 1.

It will not be 0 unless both of the PLCs set it to 0..