7

Data Table Numbers

Table

11

Contains

DigitalInput Discrepancy faults

Range for Start Value

Greater than or equal to the first digital input address for A, B, or C.

Range for End Value

Less than the start plus the maximum digital input ad- dress for A, B, or C.

14

Digital Input Autotestfaults

start>=1

end<=12228,

end<=start

 

 

 

 

 

15

Digital Input Genius faults

start>=1

end<=12228,

end<=start

 

 

 

 

 

16

Digital Input Point faults

start>=1

end<=12228,

end<=start

 

 

 

 

 

21

Digital Output Discrepancy faults: PLC A

start>=1

end<=12228,

end<=start

 

 

 

 

 

22

Digital Output Discrepancy faults: PLC B

start>=1

end<=12228,

end<=start

 

 

 

 

 

23

Digital Output Discrepancy faults: PLC C

start>=1

end<=12228,

end<=start

 

 

 

 

 

24

Digital Output Autotestfaults

start>=1

end<=12228,

end<=start

 

 

 

 

 

25

Digital Output Genius faults

start>=1

end<=12228,

end<=start

 

 

 

 

 

26

Digital Output Point faults

start>=1

end<=12228,

end<=start

 

 

 

 

27

Digital Logon faults (PLC A)

First group number required

Last group number required

 

 

 

 

28

Digital Logon faults (PLC B)

First group number required

Last group number required

 

 

 

 

29

Digital Logon faults (PLC C)

First group number required

Last group number required

 

 

 

 

31

Analog Input Discrepancy faults

Greater than or equal to the

Less than the start plus the

 

 

first digital input address for A,

maximum digital input ad-

 

 

B, or C.

dress for A, B, or C.

35

Analog Input Genius faults

start>=1

end<=8192,

end<=start

 

 

 

 

 

36

Analog Input Point faults

start>=1

end<=8192,

end>=start

 

 

 

 

 

37

Analog Input Low Alarms

start>=1

end<=8192,

end>=start

 

 

 

 

 

38

Analog Input High Alarms

start>=1

end<=8192,

end>=start

 

 

 

 

 

45

Analog Output Genius faults

start>=1

end<=8192,

end>=start

 

 

 

 

 

46

Analog Output Point faults

start>=1

end<=8192,

end>=start

 

 

 

 

47

Input shutdown timers (per block)

High byte contains rack num-

High byte contains the number

 

Returns a single word indicating the shutdown

ber (0±7) and low byte con-

1. Low byte contains the Serial

 

timer value as seconds of elapsed time. A value

tains slot number (1±9)

Bus Address (SBA) of the de-

 

of ±1 means a fault exists but the timer has not

 

sired block you want shut-

 

started (the Shutdown Cancel bit is On).

 

down information from (0±28)

 

 

 

 

48

Output shutdown timers (per block)

High byte contains rack num-

High byte contains the number

 

Returns a single word indicating the shutdown

ber (0±7) and low byte con-

1. Low byte contains the Serial

 

timer value as seconds of elapsed time. A value

tains slot number (1±9)

Bus Address (SBA) of the de-

 

of ±1 means a fault exists but the timer has not

 

sired block you want shut-

 

started (the Shutdown Cancel bit is On).

 

down information from (0±28)

 

 

 

 

 

49

Input shutdown timers (per GBC)

High byte contains rack num-

unused

 

 

For each SBA, returns a word indicating the

ber (0±7) and low byte con-

 

 

 

shutdown timer value as seconds of elapsed

tains slot number (1±9) where

 

 

 

time. A value of ±1 means a fault exists but the

the desired Bus Controller is

 

 

 

timer has not started (the Shutdown Cancel bit

located.

 

 

 

is On). A value of 0 means a block does not exist

 

 

 

 

or has no associated shutdown timer. All output

 

 

 

 

blocksreturn the value 0.

 

 

 

 

 

 

 

 

50

1000h

Output shutdown timers (per GBC)

For each SBA, returns a word indicating the shutdown timer value as seconds of elapsed time. A value of ±1 means a fault exists but the timer has not started (the Shutdown Cancel bit is On). A value of 0 means a block does not exist or has no associated shutdown timer. All input blocksreturn the value 0.

Configurationtextdescription

High byte contains rack num- ber (0±7) and low byte con- tains slot number (1±9) where the desired Bus Controller is located.

unused

unused

unused

GFK-0787B

Chapter 7 Programming Information

7-25