12.On the bus configuration screen, the Bus Controller appears at its configured Bus Address, 31 in this example.

13.From here, you can configure the devices on the bus, including the other bus controllers in the group. Each bus controller must be configured both individually and as a device on the bus of the other bus controller(s)

on the same bus. In addition, the bus controllers on a Global Data bus must be configured with an appropriate Global Data address and length.

When configuring I/O blocks, be sure to match I/O address assignments and serial bus addresses of GMR blocks to those made using the GMR Configuration Software.

Note: For input blocks in GMR groups, the I/O addresses configured on these screens are for the ªrawº input data received directly from the blocks (for the A, B, and C areas of the Table, as described in the Programming chapter. For output blocks in GMR groups, the output addresses configured on these screens are for the physical redundant output data (not the logical addresses used in the application program). These addresses are produced by the GMR Configuration Software, and are listed in the configuration printout.