Configuring a Triplex, Duplex, or Simplex Discrete Input Group

To configure a discrete group, click on that line, or move the cursor there and press the Return key, or press the highlighted letter key. Then select whether the blocks in the group are 16-point or 32-point blocks. For example:

'

A configuration screen like the one shown above right appears. To item on this screen, use the Tab key or mouse.

ID

Enter a name or a description of up to 12 characters, such as

 

ªin group 3º. This entry is for your information only. It is not used by

 

the GMR software.

Start %I

Enter the starting %I Input Table reference for the group. This is the %I

 

address of the voted input data. The actual %I references used for the

 

input data from each block are configured using the Logicmaster 90

 

software. This configuration utility will provide a printout of the addressing

 

required for Logicmaster 90. The allowable reference ranges are:

0001 to 0112 (788 CPU)

0001 to 2048 (789 CPU)

Duplicate addresses are not allowed within a GBC group. You will not be permitted to continue until you have entered a unique address.

SBA

Enter a serial bus address (also referred to as the ªdevice numberº) from

 

0 to 28. Duplicate bus addresses are also not permitted within a GBC

 

group. However, each block in the group uses the same serial bus address on its

 

respective bus.

6-28

GeniustModular Redundancy Flexible Triple Modular Redundant (TMR) System

GFK-0787B

 

User's Manual ± March 1995

 