Logicmaster Configuration Summary

1.Change the CPU to the correct type (in this example, it is a CPU 789) and add appropriate memory.

2.Move the cursor to the rack and slot location for the first Bus Controller.

Be sure the location matches the entry made with the GMR Configuration Software.

3.Press F2 (genius).

4. From the Catalog # screen, press F1 (gbc).

5.From the Description screen, press Enter.

6.Complete the entries on the left side of the screen. Remember that all of the bus controllers in the PLC must have the same serial bus address (31 in the illustration at right). Leave the Ref Adr Chk selection disabled (the default).

7.On the right side of the screen, leave Redund mode set to NONE. The entries below it cannot then be edited.

8. If this Bus Controller was configured in the INIT DATA window of the Configuration utility, for Global Data, set the field for Config Mode to MANUAL. Enter a beginning %R reference and length (64) for global data. See the Programming chapter of this book for more information about Global Data addressing.

9.Press the ESC key to return to the rack configuration screen.

10.The rack configuration screen now includes the Bus Controller.

11.Press F10 (zoom) to go to the bus configuration screen.