1rsdd

Message

GMR12±tmplt too small GMR15±IS x at y

GMR15±ST x at y

GMR15±IW x GMR15±tmplt too small

Unauthorized GMR Access Incorrect GMR Version GMR Software Exception Invalid GMR Pointer More than 1 Master Invalid Switch Case Discrep NAK PLC A Discrep NAK PLC B Discrep NAK PLC C Disc results read fault DQ x.y.1.z ±> d/f/s

CQ x.y.1.z ±> d/f/s

Xtalk results read flt

CR fail x.y.l.zf/s

Trans x.y.l.zcccccccc

Null timeout from PLC A Null timeout from PLC B Null timeout from PLC C I/OS/Dr.s.b.d I/OS/Dcancelr.s.b.d I/OS/D8hrsr.s.b.d I/OS/D1hrr.s.b.d

I/PA/Trestimeout

Meaning

GMR14 has detected an internal error condition

GMR15 state machine went to step x (illegal). Step no. at offset y in GMR15 diagnos- tics

GMR15 state mach. exceeded allowed time in step x. Step no. at offset y in GMR15 diag- nostics

GMR15 has output an illegal waycode of x GMR14 has detected an internal error condition

GMR15 was invoked with incorrectpassword

GMR15 version number does not match the GMR system version number An invalid call number was detected

The error code pointer was out of bounds

GMR15 detected that more than 1 PLC was operating as master GMR detected an illegal internal condition

PLC A failed to acknowledge discrepancy results PLC B failed to acknowledge discrepancy results PLC C failed to acknowledge discrepancy results

The PLC was unable to read output discrepancy results data from the master PLC

The PLC expected to dequeue an input autotest results datagram from the device at rack x, slot y, SBA (serial bus address) z. Instead, an invalid datagram was dequeued with function code f and subfunction code s from SBA (bus address) d

The PLC expected no datagram to be in the queue for the device at rack x, slot y, seri- al bus address z. Instead, an invalid datagram was found with function code f, and subfunction code s, from serial bus address d

Non-master could not read input autotest results from master PLC

COMREQ with function code f and subfunction code s failed when sent to the device at rack x, slot y, SBA z

Output discrepancy processing could not be completed for the channels marked in c on the device at rack x, slot y, SBA z,due to transitioning outputs

Timeout occurred while waiting for PLC A to transmit a null test number Timeout occurred while waiting for PLC B to transmit a null test number Timeout occurred while waiting for PLC C to transmit a null test number I/O Shutdown on the specified block

I/O Shutdown cancelled on the specified block I/O Shutdown in 8 hours on the specified block I/O Shutdown in 1 hour on the specified block

A/T results for SBA dd on GBC at rack r slot s

5-22

GeniustModular Redundancy Flexible Triple Modular Redundant (TMR) System

GFK-0787B

 

User's Manual ±March 1995

 

Page 82
Image 82
GE GFK-0787B user manual Code