Configuring GMR Bus Controllers and I/O Blocks

Each bus controller that serves the same input and/or output groups is configured similarly; so it is usually easiest to copy the first completed bus/bus controller in a group to configure the other bus controller(s) in the same group. Any additional changes can be made to the individual bus controller/bus configurations as needed (for example, to accommodate non-voted I/O on a bus, or the ªDº block of a 4-block output group.

GMR redundant input blocks in a group each have a unique ªrawº data address on each bus in the same PLC. However, the blocks have the same reference addresses in another GMR PLC.

GMR redundant outputs in a group have the same reference addresses on each bus in the group.