4

output states of the blocks, the block does not use those outputs in its output voting. The block(s) continue to ignore outputs from the PLC until they match those of the block's voted outputs or until commanded to do so by setting the FORCLOG command bit (%M12263). This is covered on more detail on page 7-17.

Startup requires multiple PLC sweeps to complete. Execution of the application program should not be started until initialization and synchronization have been completed successfully.

Online Changes

The GMR configuration can be set up to either permit or reject online program changes. These changes result in checksum mismatches. Such mismatches are handled as described below by the PLCs in the system.

Typeof Mismatch

Configured to Allow Changes

Configured to RejectChanges

orChange

 

 

 

 

Detected

Changed/StartedPLC

Other PLC(s)

Changed/StartedPLC

OtherPLC(s)

 

 

 

 

 

Program Checksum

ªProgramMismatchº

ªProgramMismatchº

ªProgram Mismatchº mes-

No Action

mismatch at startup

message logged

message logged

sage logged. PLC stopped

 

 

 

 

 

 

( Following PLC Fault

ªProgramMismatchº

ªProgramMismatchº

N/A ± PLC is stopped

No Action

Reset)

messagere-logged

messagere-logged

 

 

 

 

 

 

 

Program Checksum

ªProgram Changeº mes-

ªProgram Changedº mes-

ªProgram Changedº mes-

No Action

change while running

sage logged

sage logged

sage logged

 

 

 

 

PLC stopped

 

 

 

 

 

 

( Following PLC Fault

ªProgramMismatchº

ªProgramMismatchº

N/A ± PLC is stopped

No Action

Reset)

message logged

message logged

 

 

 

 

 

 

 

GMRConfiguration

ªGMR Configuration

No Action

ªGMR Configuration

No Action

Checksummismatch

Mismatchº and ªPro-

 

Mismatchº and ªProgram

 

at startup

gram Mismatchº mes-

 

Mismatchºmessages

 

 

sages logged. PLC

 

logged. PLC stopped

 

 

stopped

 

 

 

 

 

 

 

 

( Following PLC Fault

N/A ± PLC is stopped.

No Action

N/A ± PLC is stopped

No Action

Reset)

 

 

 

 

 

 

 

 

 

ConfigurationCheck-

ªGMR Configuration

ªGMR Configuration

ªGMR Configuration

No Action

sum mismatch while

Changedº and ªProgram

Changedº and ªProgram

Changeº and ªProgram

 

running

Changedº messages

Changedº messages

Changedº messages

 

 

logged.

logged.

logged. PLC stopped

 

 

 

 

 

 

( Following PLC Fault

ªGMR Configuration

ªGMR Configuration

N/A ± PLC is stopped

No Action

Reset)

Mismatchºmessage

Mismatchºmessage

 

 

 

logged.

logged

 

 

 

 

 

 

 

In all cases, a fault message is logged into the PLC Fault Table.

If the fault condition remains after the PLC Fault is reset, the message is relogged. The message indicates which PLC has changed, or which mismatches.

A change to the GMR Configuration information takes effect only when the PLC is transitioned from Stop to Run mode. Therefore, the PLC should be placed in Stop mode before downloading a new GMR Configuration.

Autotesting is suspended if a PLC is started up with a new configuration. After all PLCs have been given the same configuration, autotesting will resume.

GFK-0787B

Chapter 4 PLC Subsystem

4-3

Page 41
Image 41
GE GFK-0787B user manual Online Changes