5

Code

10814

10815

10817

10818

10819

10820

10821

10822

10823

10824

10825

10826

10827

10828

10829

10830

10831

10832

10833

10834

10835

10837

10840

10841

10842

10843

10844

10850

10851

10852

10853

10860

10861

10862

10863

10864

10865

10866

10867

10870

10871

10872

10894

10898

10899

10902

Message

GMR cfg err no of PLCs GMR cfg errW/dogtimer GMR Cfg Err %R usage GMR cfg err %AI Usage GMR cfg err comreq %R

GMR cfg err Tx global

GMR cfg err Rx global

GMR cfg err I/O > max

GMR cfg err voted DIN

GMR cfg err voted AIN

GMR cfg errredundO/P

GMR cfg err alpha rack GMR cfg err alpha slot GMR cfg err beta rack GMR cfg err beta slot GMR cfg err %M sync GMR cfg err %R sync GMR cfg err %R temp

GMR cfg err%RA/Tint

GMR cfg err ssu flt act GMR cfg err syc flt act GMR cfg err no of GBCs GMR version MM.mmE Cfg util ver MM.mmE GMR config crc 0xXXXX

XXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXX InvalidDigI/Pdata Invalid NV Dig I/P data InvalidAnaI/Pdata InvalidNVAnaI/Pdata GMR cfg err %R Write GMR cfg err %AI Write GMR cfg err %AQ Write GMR cfg err %I Write GMR cfg err %Q Write GMR cfg err %T Write GMR cfg err %M Write GMR cfg err %G Write Shutdown in hh mm ss Shutdown Cancelled SystemShutdown

Config changed r.s.b.d. GMR Fault Handler Error GMR Fault Handler Error

User_IF±GMR version

Meaning

GMR Configuration Module detected more than 3 PLCs in the config data GMR Configuration Module detected invalid watchdog time in the config data GMR Configuration Module detected insufficient %R registers

GMR Configuration Module detected insufficient PLC Analog Inputs

GMR Configuration Module detected invalid positioning of the comreq status %R area

GMR Configuration Module detected invalid positioning of the Tx global comms %R area

GMR Configuration Module detected invalid positioning of the Rx global comms %R area

GMR Configuration Module detected that the maximum I/O points has been exceed- ed

GMR Configuration Module detected that the maximum number of voted digital inputs has been exceeded

GMR Configuration Module detected that the maximum number of voted analog inputs is exceeded

GMR Configuration Module detected that the maximum number of redundant out- puts is exceeded

GMR Configuration Module detected that alpha inter-PLC GBC is in an invalid rack GMR Configuration Module detected that alpha inter-PLC is in an invalid slot GMR Configuration Module detected that beta inter-PLC is in an invalid rack GMR Configuration Module detected that beta inter-PLC is in an invalid slot GMR Configuration Module detected invalid positioning of the %M sync area GMR Configuration Module detected invalid positioning of the %R sync area

GMR Configuration Module detected invalid positioning of the %R temp %M sync area

GMR Configuration Module detected invalid positioning of the %R autotest interval pointer

GMR Configuration Module detected invalid system startup fault action GMR Configuration Module detected invalid startup sync fault action GMR Configuration Module detected invalid number of GBCs

GMR software version number GMR config utility version number Config utility CRC value

First 20 characters of config description Remaining characters of description

Invalid data detected in voted digital input record Invalid data detected in nonvoted digital input record Invalid data detected in voted analog input record Invalid data detected in nonvoted analog input record %R register external device write access range is invalid %AI register external device write access range is invalid %AQ register external device write access range is invalid %I register external device write access range is invalid %Q register external device write access range is invalid %T register external device write access range is invalid %M register external device write access range is invalid %G register external device write access range is invalid

Systemsimplex shutdown in hh hours, mm minutes and ss seconds Systemsimplex shutdown cancelled

System has shut down

The block-level configuration was changed by the specified device. Fault handler received a fault for an invalid discrete block

Fault handler received a fault for an invalid analod block

Module version number does not match the GMR system version number

5-20

GeniustModular Redundancy Flexible Triple Modular Redundant (TMR) System

GFK-0787B

 

User's Manual ±March 1995

 

Page 80
Image 80
GE GFK-0787B user manual Code