Discrete Input Fault Contacts for GMR

In the discrete Input Table there are fault contacts associated with each item of voted input data, non-voted input data, and ªrawº data input from bus A, B, and C:

Discrete Input Table

Input

 

Voting

 

Logic

 

Bus A inputs

A

 

Bus B inputs

B

 

Bus C inputs

C

Voted Inputs

Non-voted Inputs

Reserved inputs

Fault contacts are set for:

HInput Genius faults

HInput discrepancy faults for A, B, and C inputs

HInput autotest faults

HLine faults

See page 5-25 for detailed information on conditions that cause fault contacts to be set.

Discrete Output Fault Contacts for GMR

For discrete outputs, fault contacts are associated with logical outputs (outputs from the application program). These logical references are copied to the physical output references. If a fault is detected on a physical output, the fault contact associated with that output's logical reference is set.

Contact References Associated with an Output

 

Logical

Physical

reference

reference

Fault

 

contact

 

Fault contacts are set for:

HGenius faults

HDiscrepancy faults

HAutotest faults

See page 5-26 for detailed information on conditions that cause fault contacts to be set.

7-22

GeniustModular Redundancy Flexible Triple Modular Redundant (TMR) System

GFK-0787B

 

User's Manual ± March 1995

 