Chapter 12 Error Code List and Special Internal Outputs
12-12
No. Name Stored data Description Setting
condition
Resetting
condition
WRF06B Pulse and PWM
output auto
correction setting
01: For EH-***DTP
02: For EH-***DT
03: For EH-***DRP
04: For EH-***DRT
The output waveforms of the pulses and
PWM are automatically corrected by
setting the value corresponding to the
CPU model.
WRF06C Potentiometer CH1
WRF06D Potentiometer CH2
Sampling number: 0 to 40.
WRF06E Analog input type
selection
Selects whether the analog input is voltage or current.
a: Analog 1 selection 0=Voltage 1=Current
b: Analog 2 selection 0=Voltage 1=Current
WRF06F Counting mode of
2-phase counter
00: Mode 0 01: Mode 1
02: Mode 2 03: Mode 3
WRF070 I/O operation mode H00: Mode 0
H01: Mode 1
H02: Mode 2
H03: Mode 3
H10: Mode 10
WRF071 I/O detailed function
settings
I/O assignment for counter, PWM and pulse train output
WRF072
to F075
Output frequency,
On-preset value
Frequency setting value, on-preset setting value
WRF076
to F079
On-duty value,
Off-preset value
On-duty setting value, off-preset setting value
WRF07A
to F07D
Pre-load value,
Pulse output value
Counter pre-load value or pulse output value
WRF07E Input edge Counter input edge setting value
WRF07F Input filtering time Filter time ×0.5 ms, up to 40 (=20ms)
Set by user Cleared by
user
WRF080
to F19F
Undefined Do not use.
*: See Chapter 8 for more details.
15 14 13 0
ab Not used