Chapter 9 PLC Operation

Chapter 9 PLC Operation

The operating status and stop status of the MICRO-EH can be switched through various types of operations. This feature is shown in Figure 9.1.

Cancel operation definition input

 

 

Switch “RUN” and

 

 

operation definition

Switch “RUN”

 

input “ON”

Stop status

Operating status

Stop status

Switch “STOP”

 

Switch “STOP” or

 

 

operation definition

 

 

input “OFF”

Designate operation definition input

 

 

 

 

 

Caution

 

 

The MICRO-EH cannot handle a REMOTE

 

 

specification. A 10-point type CPU becomes

 

 

the RUN mode when the RUN input is On.

 

 

 

Figure 9.1 Transitional diagram between operating and stop statuses

The MICRO-EH can be operated or stopped under the conditions as shown in Figure 9.1. If an error is detected during operation or stop, output is shut off, an error is displayed and the MICRO-EH stops. There are fatal error, serious error, minor error and warning. The operating status for each error is listed in Table 9.1.

Table 9.1 Description of each error and operating status

Classification

Description

Run/Stop

Fatal error

This indicates there is a fatal and unrecoverable error, such as a power

Stops

 

supply problem, microcomputer error, system ROM error, system RAM

 

 

error and system path error.

 

Serious error

This indicates there is an error such as data memory problem, system

Stops

 

program problem, user memory problem, user memory size error,

 

 

syntax/assembler error, etc., which may cause a malfunction if operation is

 

 

continued.

 

Minor error

These are errors such as I/O information verify error, remote problem,

Stops

 

congestion error, excessively assigned I/O points, etc. The operation may be

(continued operation

 

continued when a continue operation is set by the user programs.

is possible if

 

 

specified)

Warning

These are problems such as a transfer error, backup memory write problem,

Operation continues

 

etc. where it is possible to continue the operation.

 

9-1

Page 234
Image 234