Chapter 12 Error Code List and Special Internal Outputs
12-10
No. Name Storage data Description Setting
condition
Resetting
condition
WRF03C Port 1
Modem timeout time
a: Whether or not settings are present 0=No setting
1=Setting is present
Modem timeout time: 1 second increments (set with hexadecimal
value)
0=No timeout monitoring
Set by user Cleared by
user
WRF03D Port 2
Communication
settings
a: Setting bit 1=Set Set to 0 by the system after setting is
complete.
b: Transmission control procedures 0=Standard, 1=Simplified
c: Whether or not station numbers are present 0=No station
numbers, 1=Station numbers are present
d: Baud rate settings
= 00000: 4800 bps, = 00001: 9600 bps, = 00010: 19.2 kbps
= 00011: 38.4 kbps, = 4800 bps if other than the above
Station numbers: 2 digits from 00 through 31 of BCD
Set to 31 for values outside the range
Set by user Cleared by
user
WRF03E Potentiometer input 1 0 - 1023 Set by user Cleared by
user
WRF03F Potentiometer input 2 0 - 1023 Set by user Cleared by
user
WRF040
to F042
Occupied member
registration area 1
WRF043
to F045
Occupied member
registration area 2
WRF046
to F048
Occupied member
registration area 3
WRF049
to F04B
Occupied member
registration area 4
Occupied port number
a: 0=Not occupied, 1=Read-occupied, 2=Write-occupied
b: Loop number c: Unit number
d: Module number e: Port number
Set by the
system
Cleared by
the system
WRF04C
to F04F
Undefined Do not use.
WRF050 System ROM version System software version in internal ROM
WRF051 System ROM version System software version in external FLASH memory
Set by the
system -
WRF052 Undefined Do not use.
WRF053 Undefined Do not use.
WRF054 Power on timer Power on time [sec.] (low word)
WRF055 Power on timer Power on time [sec.] (high word)
Set by the
system -
WRF057 Detailed information
of counter setting
errors
a: Error in pulse frequency total
b: Pulse 4 frequency c: Pulse 3 frequency
d: Pulse 2 frequency e: Pulse 1 frequency
f: Counter 4 preset g: Counter 3 preset
h: Counter 2 preset i: Counter 1 preset
0=Normal, 1=Error
Set by the
system
Cleared by
the system
15 8 7 0
aNot used Modem timeout time
15 14 13 12 8 7 0
abc d Station number
15 8 7 0
aFixed to 0
bc
de
1514 876543210
aNot used bcdefghi