Chapter 12 Error Code List and Special Internal Outputs

Error

Error name

Classifi

 

RUN

OK

Ope-

Related special

Description

internal output

code

[detection timing]

-cation

LED

LED

ration

 

Bit

Word

 

 

 

 

 

 

 

5F

Backup memory error

Warning

Data cannot be written to the backup

*1

 

Run

 

[at program downloading

 

memory.

 

 

 

 

 

 

and special I/O function

 

 

 

 

 

 

 

 

setting is requested]

 

 

 

 

 

 

 

61

Port 1 transmission error

Warning

Parity error was detected during

*1

 

Run

 

(parity)

 

transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

62

Port 1 transmission error

Warning

Framing error or overrun error was

*1

 

Run

 

(framing/overrun)

 

detected during transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

63

Port 1 transmission error

Warning

Time out error was detected during

*1

 

Run

 

(time out)

 

transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

64

Port 1 transmission error

Warning

Protocol (transmission procedure)

*1

 

Runs

 

(protocol error)

 

error was detected during transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

65

Port 1 transmission error

Warning

Checksum error was detected during

*1

 

Run

 

(BCC error)

 

transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

67

Port 2 transmission error

Warning

Parity error was detected during

*1

 

Run

 

(parity)

 

transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

68

Port 2 transmission error

Warning

Framing error or overrun error was

*1

 

Run

 

(framing/overrun)

 

detected during transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

69

Port 2 transmission error

Warning

Time out error was detected during

*1

 

Run

 

(time out)

 

transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

6A

Port 2 transmission error

Warning

Protocol (transmission procedure)

*1

 

Run

 

(protocol error)

 

error was detected during transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

6B

Port 2 transmission error

Warning

Checksum error was detected during

*1

 

Run

 

(BCC error)

 

transmission.

 

 

 

 

 

 

[when transmitting]

 

 

 

 

 

 

 

71

Battery error

Warning

• Battery voltage dropped below the

*1

 

Run

R7D9

*3

(data memory)

 

specified value

 

 

 

 

 

 

[always checking]

 

• Battery not installed

 

 

 

 

 

72

Instantaneous power

Warning

Instantaneous power failure detected.

*1

 

Run

R7CF

*4

failure detection

 

 

 

 

 

R7DA

 

 

[always checking]

 

 

 

 

 

 

 

94

Port 1

Warning

There is no response with the AT

*1

 

Run

 

No modem response

 

command.

 

 

 

 

 

 

[when modem is

 

 

 

 

 

 

 

 

connected]

 

 

 

 

 

 

 

*1: Depends on the CPU’s operating state. The RUN LED is lit while the CPU is in operation; the RUN LED is unlit while the CPU is not in operation.

*2: Depending on the settings of the operating parameters from the peripherals, the operation may be continued even when an error occurs.

*3: Although batteries cannot be mounted on the 10- or 14-point type, battery errors are monitored by the system. Set R7EE to OFF prior to the use.

*4: Supported by software version 1.11 (WRF051=H0111) or newer.

How to Clear the CPU Error Code:

Set 1 to the Special Internal Output R7EC.

12-2

Page 265
Image 265
Hitachi NJI-350B manual Error Error name Classifi, Code Detection timing Cation, R7CF, Failure detection, 12-2