Toshiba RAV-SM802CT-E Revised Mar, P19 error, F02 error, Is voltage applied, Defect ÆReplace

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 92
Image 92

Revised : Mar. 2007

[P19 error]

NO

Check and replace electron expansion valve.

NO

Is operation of

4-way valve normal?

YES

Is flow of refrigerant by electron expansion valve normal?

YES

Are characteristics

of TC sensor resistance

value normal?

NO

Is voltage applied

NO

 

to 4-way valve coil terminal

 

 

in heating operation?

 

 

YES

 

 

 

 

Check 4-way valve

Defect ÆReplace

NO

Is circuit cable normal?

YES

Check and correct circuit.

*Refer to Characteristics-2. YES

Replace TC sensor.

Check indoor P.C. board.

Defect ÆReplace

NO

Check CDB P.C. board.

YES

Check CDB P.C. board.

Defect ÆReplace

* For RAV-SM563AT-E,SM803AT-E, check control P.C. board.

In cooling operation, if high pressure is abnormally raised, [P19 error] / [08 error] may be displayed.

In this case, remove cause of pressure up and then check again referring to the item [P04 error] / [21 error].

[F02 error]

Is connection of TC sensor connector

NO

 

(Indoor P.C. board CN101) normal?

 

 

YES

 

 

 

 

 

 

Correct connection of connector.

Are characteristics of

TC sensor resistance value normal?

YES

Check indoor P.C. board (MCC-1402).

Defect ÆReplace

NO

* Refer to Characteristics-2.

Replace TC sensor.