Toshiba RAV-SM803AT-E Part name, Procedure, Remarks, Flange, Loosen by turning, clockwise

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 146
Image 146

No.

Part name

 

Procedure

Remarks

 

 

 

Fan motor

1) Perform works of items 1) to 5), 7) of

 

 

 

2)

Remove the flange nut fixing the fan

Flange

 

 

 

motor and the propeller fan.

 

 

 

• Loosen the flange nut by turning clock-

nut

 

 

 

 

 

 

 

wise. (To tighten the flange nut, turn it

 

 

 

 

counterclockwise.)

 

 

 

3)

Remove the propeller fan.

 

 

 

4)

Remove the lead wire from the hook fixing

 

 

 

 

the fan motor lead wires on the motor

 

 

 

 

base. (Three positions)

Loosen by turning

 

 

5)

Disconnect the connector for fan motor

 

 

clockwise

 

 

 

from the inverter.

 

6)Take off the fixing screws (4 pcs.) while holding by hands so that the fan motor does not fall.

*(Note)

Tighten the flange nut with torque 9.8N•m (100kgf/cm).

Propeller fan

Fan motor

Motor base

Fixing claws for

 

fan motor lead

 

wires (3 positions)

– 146 –

Page 146
Image 146
Toshiba RAV-SM803AT-E Part name, Procedure, Remarks, Flange, Loosen by turning, clockwise, Propeller fan Fan motor