7. REFRIGERANT R410A

This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.

The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refriger- ating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.

The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.

7-1. Safety During Installation/Servicing

As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi- als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.

1.Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.

If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.

2.Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.

The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi- tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.

3.If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.

If the refrigerant gas comes into contact with fire, a poisonous gas may occur.

4.When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.

5.After completion of installation work, check to make sure that there is no refrigeration gas leakage.

If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

6.When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.

If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.

7.Be sure to carry out installation or removal according to the installation manual.

Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.

8.Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.

Improper repair’s may result in water leakage, electric shock and fire, etc.

7-2. Refrigerant Piping Installation

7-2-1. Piping Materials and Joints Used

For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.

1.Copper Pipes

It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.

As an air conditioner using R410A incurs pres- sure higher than when using R22, it is necessary to choose adequate materials.

Thicknesses of copper pipes used with R410A are as shown in Table 7-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.

NOTE:

Refer to the 7-6. Instructions for Re-use Piping of R22 or R407C”.

– 51 –

Page 51
Image 51
Toshiba RAV-SM802BT-E, RAV-SM1102CT-E, RAV-SM803AT-E Safety During Installation/Servicing, Piping Materials and Joints Used

RAV-SP1102UT-E, RAV-SM562BT-E, RAV-SM562CT-E, RAV-SM563AT-E, RAV-SM802BT-E specifications

Toshiba, a prominent player in the HVAC sector, has engineered a range of advanced air conditioning systems that cater to diverse environments and needs. Among their standout offerings are the RAV-SM562BT-E, RAV-SM1102CT-E, RAV-SM563AT-E, RAV-SM1403UT-E, and RAV-SM803UT-E models. Each of these systems embodies Toshiba's commitment to energy efficiency, innovative technology, and user-centric design.

The RAV-SM562BT-E model is designed for residential and light commercial use, boasting a cooling capacity of 5.6 kW and a heating capacity of 6.7 kW. It incorporates Toshiba’s advanced inverter technology, ensuring optimal performance and reduced energy consumption. The unit features a sleek, modern design and operates quietly, making it perfect for environments where noise levels must be controlled.

Next in line is the RAV-SM1102CT-E, which excels in larger commercial spaces. With a remarkable cooling output of 11.2 kW and heating performance to match, this unit is engineered for heavy-duty usage. It employs a multi-split system, allowing several indoor units to connect to a single outdoor unit. This provides homes or businesses with flexible installation options without sacrificing comfort or style.

The RAV-SM563AT-E model presents a perfect blend of efficiency and effectiveness, focusing on eco-friendliness. With an impressive seasonal energy efficiency ratio (SEER), it minimizes energy bills while maintaining superior performance. This model is equipped with advanced filtration technology that not only cools or heats the air but also improves indoor air quality by capturing dust and allergens.

Designed for high-performance requirements, the RAV-SM1403UT-E offers cooling and heating capacities of 14.0 kW. This unit is hardy enough for industrial applications but remains efficient and easy to operate. The incorporation of Toshiba’s Smart Control technology allows users to manage their systems remotely, enhancing convenience.

The RAV-SM803UT-E completes the lineup, combining 8.0 kW cooling and heating outputs with cutting-edge technology. It features adaptive comfort control, which adjusts the temperature based on occupancy and external conditions, ensuring optimal comfort while maintaining energy efficiency.

In conclusion, Toshiba's range of RAV-SM series models offers innovative features, advanced technology, and effective performance. These models not only meet the demands of modern spaces but also shine in energy efficiency, making them excellent choices for both residential and commercial applications. By addressing the diverse requirements of users, Toshiba continues to uphold its reputation as a leader in HVAC solutions.