Toshiba RAV-SM803AT-E, RAV-SM1102CT-E, RAV-SM1102BT-E, RAV-SM1403UT-E Revised Mar, Outdoor Unit

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 48
Image 48

Revised : Mar. 2007

6-2. Outdoor Unit

RAV-SM563AT-E

No.

Parts name

Type

 

Specifications

 

 

 

 

1

Fan motor

ICF-140-43-4R

Output (Rated) 43 W

 

 

 

 

2

Compressor

DA150A1F-20F

3 phase, 4P, 1100 W

 

 

 

 

3

Reactor

CH-57

10 mH, 16A

 

 

 

 

 

4

Outdoor temp. sensor (To-sensor)

10 k

at 25°C

 

 

 

 

 

5

Heat exchanger sensor (Te-sensor)

10 k

at 25°C

 

 

 

 

 

6

Suction temp. sensor (Ts-sensor)

10 k

at 25°C

 

 

 

 

 

7

Discharge temp. sensor (Td-sensor)

50 k

at 25°C

 

 

 

 

8

Fuse (Switching power (Protect))

T3.15 A, AC 250 V

 

 

 

 

9

Fuse (Inverter, input (Current protect)

25 A, AC 250 V

 

 

 

 

 

10

4-way valve solenoid coil

STF-01AJ502E1

 

 

 

 

 

11

Compressor thermo. (Protection)

US-622

OFF : 125 ± 4°C, ON : 90 ± 5°C

 

 

 

 

 

12

Coil (Pulse Motor Valve)

CAM-MD12TF-6

 

 

 

 

 

 

RAV-SM803AT-E

No.

Parts name

Type

 

Specifications

 

 

 

 

1

Fan motor

ICF-140-43-4R

Output (Rated) 43 W

2

Compressor

DA150A1F-20F

3 phase, 4P, 1100 W

3

Reactor

CH-57

10 mH, 16 A

4

Outdoor temp. sensor (To-sensor)

10 k

at 25°C

5

Heat exchanger sensor (Te-sensor)

10 k

at 25°C

6

Suction temp. sensor (Ts-sensor)

10 k

at 25°C

7

Discharge temp. sensor (Td-sensor)

50 k

at 25°C

8

Fuse (Switching power (Protect))

T3.15 A, AC 250 V

9

Fuse (Inverter, input (Current protect))

25 A, AC 250 V

10

4-way valve solenoid coil

STF-01AJ502E1

AC 220 – 240 V

11

Compressor thermo. (Protection)

US-622

OFF : 125 ± 4°C, ON : 90 ± 5°C

12

Coil (Pulse Motor Valve)

CAM-MD12TF-6

 

 

 

 

 

 

RAV-SM1103AT-E

No.

Parts name

Type

 

Specifications

 

 

 

 

1

Fan motor

ICF-280-100-1R

Output (Rated) 100 W

 

 

 

 

2

Compressor

DA420A3F-21M

3 phase, 4P, 2000 W

 

 

 

 

3

Reactor

CH-62

6 mH, 18.5 A

 

 

 

 

 

4

Outdoor temp. sensor (To-sensor)

10 k

at 25°C

 

 

 

 

 

5

Heat exchanger sensor (Te-sensor)

10 k

at 25°C

 

 

 

 

 

6

Suction temp. sensor (Ts-sensor)

10 k

at 25°C

 

 

 

 

 

7

Discharge temp. sensor (Td-sensor)

50 k

at 25°C

 

 

 

 

8

Fuse (Switching power (Protect))

T3.15 A, AC 250 V

 

 

 

 

9

Fuse (Inverter, input (Current protect)

25 A, AC 250 V

 

 

 

 

10

4-way valve solenoid coil

STF-01AJ502E1

AC 220 – 240 V

 

 

 

 

11

Compressor thermo. (Protection)

US-622

OFF : 125 ± 4°C, ON : 90 ± 5°C

 

 

 

 

 

12

Coil (Pulse Motor Valve)

UKV-U048E

 

 

 

 

 

 

– 48 –

Page 48
Image 48