Toshiba RAV-SM1102CT-E, RAV-SM1102BT-E, RAV-SM1403UT-E, RAV-SM803AT-E Part name, Procedure, Remarks

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 126
Image 126

No.

Part name

 

Procedure

Remarks

 

 

 

 

Heat

1. Detachment

 

 

exchanger

1) Recover refrigerant gas.

 

 

 

2)

Remove refrigerant pipe at the indoor

 

 

 

 

unit side.

 

 

 

3)

Perform works of items 1 of , 1 of

Fixing screws

 

 

 

, 1 of ƒ, 1 of and 1 of .

 

 

 

4)

Remove screws fixing the pipe cover.

 

 

 

 

(Ø4 × 8, 2 pcs.)

 

 

 

5)

Remove the heat exchanger by

 

 

 

 

removing fixing band and fixing screws

 

 

 

 

while holding the heat exchanger.

 

 

 

 

(Ø4 × 8, 3 pcs.)

 

 

 

2. Attachment

Fixing band

 

 

1)

Fix the parts, heat exchanger, fixing

 

 

 

 

band, pipe cover, drain cap, drain pan,

 

 

 

 

bell mouth, and electric parts box

 

 

 

 

successively to their original positions.

 

 

 

2)

Connect connectors, earth lead wire,

 

 

 

 

indoor/outdoor inter-unit cable, and

 

 

 

 

remote controller cable which have

 

 

 

 

been disconnected in the above item 1

 

 

 

 

as before.

 

 

 

3)

Connect the refrigerant pipe as before,

 

 

 

 

and then perform vacuuming.

 

 

 

 

 

Fixing screws

 

 

 

 

 

– 126 –