10-3. Error Mode Detected by LED on Outdoor P.C. Board

RAV-SM1103AT-E, RAV-SM1403AT-E /

RAV-SP562AT-E, RAV-SP802AT-E, RAV-SP1102AT-E, RAV-SP1402AT-E

<SW801: LED display in bit 1, bit 2 OFF>

When multiple errors are detected, the latest error is displayed.

When LED display is ¡ (Go on), there is the main cause of trouble on the objective part of control at CDB side and the unit stops.

When LED display is ¥ (Flash), there is the main cause of trouble on the objective part of control at IPDU side and the unit stops.

When case thermostat operates, the communication is interrupted on the serial circuit. If continuing the case thermostat operation, a serial communication error occurs because serial sending to the indoor unit is interrupted.

 

 

 

Check code

 

LED display

 

 

No.

Item

 

 

 

 

 

 

 

Type A

Type B

D800

D801

D802

D803

 

 

 

 

 

 

(Red)

(Yellow)

(Yellow)

(Yellow)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

TE sensor error

F06

18

¡

l

l

l

 

 

 

 

 

 

 

 

 

 

2

TD sensor error

F04

19

¡

¡

l

l

 

 

 

 

 

 

 

 

 

 

3

TS sensor error

F06

18

l

l

¡

l

 

 

 

 

 

 

 

 

 

 

4

TO sensor error

F08

1B

l

¡

l

l

 

 

 

 

 

 

 

 

 

 

5

Discharge temp. error

P03

1E

l

¡

¡

l

 

 

 

 

 

 

 

 

 

 

6

DC outdoor fan error

P22

1A

¡

¡

¡

l

 

 

 

 

 

 

 

 

 

CDB side

 

Communication error

 

 

 

l

l

 

7

between IPDU

L29

1C

¡

¡

 

 

 

(Abnormal stop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

High-pressure release

P04

21

l

 

l

 

 

operation

 

¡

¡

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

EEPROM error

¡

¡

l

¡

 

 

 

 

 

 

 

 

 

 

 

Communication error

 

 

l

l

 

 

 

10

between IPDU

¡

¡

 

 

(No abnormal stop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

IGBT short-circuit

P26

14

¥

l

l

l

 

protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IPDU side

12

Detection circuit error

P29

16

l

¥

l

l

 

 

 

 

 

 

 

 

13

Current sensor error

H03

17

¥

¥

l

l

 

 

 

 

 

 

 

 

 

 

 

14

Comp. lock error

H02

1D

l

l

¥

l

 

 

 

 

 

 

 

 

 

 

15

Comp. breakdown

H01

1F

¥

l

¥

l

 

 

 

 

 

 

 

 

 

¡ : Go on l : Go off ¥ : Flash (5Hz)

<<Check code>>

The check codes are classified into Type A and Type B according to the used remote controller. Be sure to check the remote controller which you use.

Type A :

Neutral 2-cores type wired remote controller such as RBC-AMT31E, RBC-AS21E2, and wireless remote controller kit such as TCB-AX21U (W)-E2.

Type B :

Polarized 3-cores type wired remote controller such as RBC-SR1-PE2,RBC-SR2-PE2, and central control remote controller such as RBC-CR64-PE2.