10-4. Troubleshooting Procedure for Each Check Code

10-4-1. Check Code

[E01 error]

Is inter-unit cable of A and B normal?

NO

 

 

 

YES

 

 

 

 

 

 

Is there no disconnection

YES

or contact error of connector on harness

 

 

from terminal block of indoor unit?

 

 

NO

 

 

 

 

 

 

NO

Is group control operation?

YES

NO

Is power of all indoor units turned on?

YES

Is power supplied to remote controller? NO

AB terminal: Approx. DC18V

 

YES

 

 

 

YES

Are two remote controllers

 

set without master unit?

 

 

NO

 

 

 

 

 

 

Correct inter-unit cable of remote controller.

Correct connection of connector.

Check circuit cables.

Check power connection of indoor unit. (Turn on power again.)

Check indoor P.C. board (MCC-1402). Defect Replace

Correct as a master unit/a sub unit (Remote controller address connector)

Check remote controller P.C. board. Defect Replace

[E09 error]

Are two remote controllers

YES

 

set without master unit?

 

 

NO

 

 

 

 

 

 

Correct as a master unit/a sub unit (Remote controller address connector)

Check remote controller P.C. board. Defect Replace