RAV-SM1403UT-E, RAV-SM1402BT-E, RAV-SM1402CT-E / RAV-SM1403AT-E

Outer diameter of refrigerant pipe

 

Gas side ØA

Liquid side ØB

 

 

 

 

 

 

15.9mm

9.5mm

 

 

 

 

 

 

 

 

 

 

 

Height difference (m)

 

 

Outdoor unit

Outdoor unit

 

 

at upper side

at lower side

 

 

30

30

 

 

 

 

 

Strainer

Indoor unit

Distributor

TCJ sensor

(Strainer incorporated)

Air heat exchanger

TC sensor

 

Refrigerant pipe

 

Refrigerant pipe

 

difference

at gas side Ø 15.9

 

at liquid side Ø 9.5

 

 

Section shape

 

 

 

of heat insulator

 

 

 

 

 

 

Height

 

 

Min.

Max.

 

 

5m

50m

 

 

 

 

 

Ball valve

 

Packed valve

 

 

Outer dia. Ø A

Outdoor unit

Outer dia. Ø B

 

 

Strainer

 

 

 

 

PMV

 

TS sensor

 

 

 

 

 

(Pulse Motor Valve)

 

TO sensor

TD sensor

(UKV-25D22)

4-way valve (STF-0213Z)

Muffler

Ø 25 × L210

Ø 25 × L180

Accumulator Rotary (2500cc) compressor

TE sensor

Heat exchanger

Outer side

Ø8, 2 rows, 20 steps FP1.3 flat fin

Inner side

Ø9.52 row, 30 steps FP1.5 flat fin

Strainer

Distributor

 

(DA420A3F – 21M)

 

 

 

 

 

 

R410A 3.0kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

 

Pressure

 

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

Indoor

temp. conditions

 

 

(MPa)

(kg/cm²G)

 

 

Indoor heat

Outdoor heat

revolutions per

 

 

Discharge

Suction

(DB/WB) (°C)

 

 

fan

 

 

second (rps)

 

 

 

 

 

 

exchanger

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

*

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

3.52

0.85

35.9

8.7

87

8

9

39

54

HIGH

27/19

35/–

Cooling

Overload

3.78

1.12

38.6

11.4

84

15

17

47

45

HIGH

32/24

43/–

 

Low load

1.51

0.71

15.4

7.2

40

7

3

23

30

LOW

18/15.5

–5/–

 

Standard

2.88

0.60

29.4

6.1

85

1

47

1

61

HIGH

20/–

7/6

Heating

Overload

3.41

1.08

34.8

11.0

81

14

54

13

24

LOW

30/–

24/18

 

Low load

2.35

0.24

24.0

2.4

80

–19

40

–16

73

HIGH

15/–

–10/(70%)

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

– 34 –

Page 34
Image 34
Toshiba RAV-SM803AT-E, RAV-SM1102CT-E, RAV-SM1102BT-E, RAV-SM1403UT-E, RAV-SM1402CT-E Revised Mar, Indoor unit, Outdoor unit