4. Wiring Specifications

Use 2-core with no polar wire.

No. of wires

Size

Match the length of wire to wire length of the central

 

 

 

Up to 1000m: twisted wire 1.25mm2

 

control system.

2

 

Up to 2000m: twisted wire 2.0mm2

 

If mixed in the system, the wire length is

 

 

 

 

 

lengthened with all indoor/outdoor inter-unit wire length at side.

 

To prevent noise trouble, use 2-core shield wire.

Connect the shield wire by closed-end connection and apply open process (insulating process) to the last terminal. Ground the earth wire to 1 point at indoor unit side. (In case of central controlling of digital inverter unit setup)

CAUTION

1)Closed-end connection of shield wire (Connect all the connecting parts of each indoor unit)

2)Apply open process to the last terminal (insulating process).

Central control device

U1 U2

3) Ground earth wire to 1 point at indoor unit side.

Caution 2

Outdoor unit

1 2 3

Indoor unit U3 U4 1 2 3

A B

Remote controller

Caution 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Central control system wiring

 

 

Caution 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: TCC-LINK adapter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(This option)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Master

 

 

 

 

 

 

 

Sub unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub unit

 

 

 

 

 

Master unit

 

 

 

 

Sub unit

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U3

U4

 

1

 

2

 

3

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

1

 

2

 

3

 

 

 

U3

U4

 

1

 

2

 

3

 

 

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Earth terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

 

Remote controller

 

 

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Group operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Triple operation)

 

 

 

 

 

 

 

 

 

 

5.P.C. Board Switch (SW01) Setup

When performing collective control by customized setup only, the setup of terminator is necessary.

Using SW01, set up the terminator.

Set up the terminator to only the adapter connected to the indoor unit of least line address No.

Central control device

U1 U2

U3 U4

Central control device

U1 U2

U3 U4

Central control devices: Max. 10 units

Refrigerant line 1

Outdoor unit

Refrigerant line 2

Refrigerant line 3

Refrigerant line 4

1 2 3

Indoor unit U3 U4 1 2 3

A B

TCC-LINK adapter ( This product ) sold separately

 

1

2

3

1

2

3

 

 

 

Master

 

 

Sub

 

 

 

unit

 

 

unit

U3 U4

1

2

3

1

2

3

 

 

A B

 

A B

 

 

 

 

Remote controller wiring

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor/outdoor inter-unit wire (AC230V serial)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Central control system wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Wiring for No.1 and 2 only

 

 

 

 

 

 

 

 

Sub unit

 

 

 

 

 

 

 

Master unit

 

 

Sub unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

 

 

U3 U4

 

1

 

2

 

3

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B

 

 

 

 

 

 

 

 

 

 

 

A B

 

 

 

 

 

 

 

A B

 

 

 

 

Remote controller

Remote controller

 

Remote controller

 

 

 

Group operation (Max. 8 units)

Remote controller

Remote controller

 

 

Twin/Triple operation (Example of triple)

Line address

1

2

 

4

 

SW01 Bit 1

ON

OF

 

OF

(OFF at shipment from factory)

SW01 Bit 2

OFF

OFF

 

OFF

(OFF at shipment from factory)

Remarks

Turn SW01 Bit 1 to ON.

As status shipped from factory

 

As status shipped from factory

 

(Reference) Setup contents of switch

 

SW01

Terminator

Remarks

Bit 1

 

Bit 1

 

 

 

OFF

 

OFF

None

Mixed with multi (Link wiring) at shipment from factory

ON

 

OFF

100

Central control by digital inverter only

OFF

 

ON

75

Spare

ON

 

ON

43

Spare

– 114 –

Page 114
Image 114
Toshiba RAV-SM1403UT-E, RAV-SM1102CT-E, RAV-SM1102BT-E 114, Wiring Specifications, C. Board Switch SW01 Setup, Size

RAV-SP1102UT-E, RAV-SM562BT-E, RAV-SM562CT-E, RAV-SM563AT-E, RAV-SM802BT-E specifications

Toshiba, a prominent player in the HVAC sector, has engineered a range of advanced air conditioning systems that cater to diverse environments and needs. Among their standout offerings are the RAV-SM562BT-E, RAV-SM1102CT-E, RAV-SM563AT-E, RAV-SM1403UT-E, and RAV-SM803UT-E models. Each of these systems embodies Toshiba's commitment to energy efficiency, innovative technology, and user-centric design.

The RAV-SM562BT-E model is designed for residential and light commercial use, boasting a cooling capacity of 5.6 kW and a heating capacity of 6.7 kW. It incorporates Toshiba’s advanced inverter technology, ensuring optimal performance and reduced energy consumption. The unit features a sleek, modern design and operates quietly, making it perfect for environments where noise levels must be controlled.

Next in line is the RAV-SM1102CT-E, which excels in larger commercial spaces. With a remarkable cooling output of 11.2 kW and heating performance to match, this unit is engineered for heavy-duty usage. It employs a multi-split system, allowing several indoor units to connect to a single outdoor unit. This provides homes or businesses with flexible installation options without sacrificing comfort or style.

The RAV-SM563AT-E model presents a perfect blend of efficiency and effectiveness, focusing on eco-friendliness. With an impressive seasonal energy efficiency ratio (SEER), it minimizes energy bills while maintaining superior performance. This model is equipped with advanced filtration technology that not only cools or heats the air but also improves indoor air quality by capturing dust and allergens.

Designed for high-performance requirements, the RAV-SM1403UT-E offers cooling and heating capacities of 14.0 kW. This unit is hardy enough for industrial applications but remains efficient and easy to operate. The incorporation of Toshiba’s Smart Control technology allows users to manage their systems remotely, enhancing convenience.

The RAV-SM803UT-E completes the lineup, combining 8.0 kW cooling and heating outputs with cutting-edge technology. It features adaptive comfort control, which adjusts the temperature based on occupancy and external conditions, ensuring optimal comfort while maintaining energy efficiency.

In conclusion, Toshiba's range of RAV-SM series models offers innovative features, advanced technology, and effective performance. These models not only meet the demands of modern spaces but also shine in energy efficiency, making them excellent choices for both residential and commercial applications. By addressing the diverse requirements of users, Toshiba continues to uphold its reputation as a leader in HVAC solutions.