12Frequency fixed <In case of wired remote controller>

operation

1.

When pushing [CHECK] button for 4 seconds or more,

(Test run)

 

[TEST] is displayed on the display screen and the

 

 

mode enters in Test run mode.

 

2.

Push [ON/OFF] button.

 

3.

Using [MODE] button, change the mode from [COOL]

 

 

to [HEAT].

 

 

• Do not use other mode than [COOL]/[HEAT] mode.

 

 

During test run operation, the temperature cannot be

 

 

 

adjusted.

 

 

An error is detected as usual.

 

 

A frequency fixed operation is performed.

 

4.

After the test run, push [ON/OFF] button to stop the

 

 

operation. (Display in the display part is same as the

 

 

procedure in item 1).)

 

5.

Push [CHECK] button to clear the test run mode.

 

 

([TEST] display in the display part disappears and the

 

 

status returns to the normal stop status.)

<In case of wireless remote controller>

(Option for 4-way air discharge cassette type only)

1.Turn off the power of the set.

Remove the adjuster with sensors from the ceiling panel.

2.Turn Bit [1: TEST] of sensor P.C. board switch [S003] from OFF to ON.

Attach the sensor P.C. board cover and mount the adjuster with sensors to the ceiling panel.

Turn on the power of the set.

3.Push [ON/OFF] button of the wireless remote control- ler and set the operation mode to [COOL] or [HEAT] using [MODE] button.

(During test run operation, all the display lamps of wireless remote controller sensors flash.)

Do not use other mode than [COOL]/[HEAT] mode.

An error is detected as usual.

A frequency fixed operation is performed.

4.After the test run, push [ON/OFF] button to stop the operation.

5.Turn off the power of the set.

Turn Bit [1: TEST] of sensor P.C. board switch [S003] from ON to OFF.

Mount the adjuster with sensors to the ceiling panel.

13 Filter sign display 1)

The operation time of the indoor fan is calculated, the [FILTER] goes on.

(Except wireless

filter reset signal is sent to the remote controller when

type)

the specified time (2500H) has passed, and it is

 

displayed on LCD.

2)

When the filter reset signal has been received from the

 

remote controller, time of the calculation timer is

 

cleared. In this case, the measurement time is reset if

 

the specified time has passed, and display on LCD

 

disappears.