Toshiba RAV-SM1102CT-E, RAV-SM1102BT-E, RAV-SM1403UT-E Error mode detected by remote controller

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 84
Image 84

– 84 –

 

 

 

 

 

Error mode detected by remote controller

 

¥: Flash, ¡: Go on, l: Go off

 

 

 

 

 

 

 

 

 

 

Wireless sensor

Wired remote controller

 

Diagnostic function

 

 

 

lamp display

 

 

 

 

 

Judgment and measures

 

 

Cause of operation

Status of

Condition

 

Operation

Timer

Ready

Check code

 

air conditioner

 

 

 

 

 

 

 

 

 

 

 

No communication with master indoor unit

Stop

Remote controller power error, Defective indoor EEPROM

 

 

 

 

Remote controller cable is not correctly

 

 

1.

Check remote controller inter-unit cables.

 

 

 

No check code is displayed.

 

connected.

 

 

2.

Check remote controller.

(Remote controller does

Power of indoor unit is not turned on.

 

 

3.

Check indoor power cables.

 

 

 

not operate.)

Automatic address cannot be completed.

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

5.

Check indoor EEPROM. (including socket insertion)

 

 

 

 

 

 

 

 

 

: Phenomenon of automatic address repetition occurred.

 

 

 

 

No communication with indoor master unit

Stop

Displayed when

Signal receiving of remote controller is defective.

¥

l

l

 

Disconnection of inter-unit cable between remote

(Automatic restart)

error is detected

1. Check remote controller inter-unit cables.

E01*2

 

controller and master indoor unit

* When there is center,

 

2.

Check remote controller.

 

 

 

 

 

(Detected at remote controller side)

 

3.

Check indoor power cables.

 

 

 

 

 

operation continues

 

 

 

 

 

 

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal sending error to indoor unit

Stop

Displayed when

Signal sending of remote controller is defective.

¥

l

l

E02

(Detected at remote controller side)

(Automatic restart)

error is detected

1. Check sending circuit inside of remote controller.

 

 

* When there is center,

 

 

: Replace remote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation continues.

 

 

 

 

 

 

 

 

 

 

 

¥

l

l

E09

Multiple master remote controllers are recognized.

Stop

Displayed when

1. Check there are multiple master units for 2 remote controllers

(Detected at remote controller side)

(Sub unit continues operation.)

error is detected

 

(including wireless).

 

 

 

 

 

 

 

 

 

: Master unit is one and others are sub units.

¥

¡

¥

L20

Duplicated indoor central addresses on

Stop

Displayed when

1. Check address setup of central control system network. (DN = 03)

communication of central control system

(Automatic restart)

error is detected

 

 

 

 

 

 

(Detected by central controller side)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*2 Check code is not displayed by wired remote controller. (Usual operation of air conditioner is disabled.) For wireless type models, E01 is notified by the display lamp.

 

 

 

 

Error mode detected by central remote controller

 

¥: Flash, ¡: Go on, l: Go off

 

 

 

 

 

 

 

 

 

Wireless sensor

Wired remote controller

Diagnostic function

 

 

 

lamp display

 

 

 

 

Judgment and measures

 

Cause of operation

Status of

Condition

 

Operation

Timer

Ready

Check code

air conditioner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C05

Sending error central remote controller

Operation continues

Displayed when

1.

Check communication line/miscabling/ Check power of indoor unit.

 

 

error is detected

2.

Check communication. (U3, U4 terminals)

 

 

 

 

 

 

 

3.

Check network adapter P.C. board.

 

 

 

 

Receiving error in central remote controller

Operation continues

Displayed when

4.

Check central controller

C06

 

 

error is detected

5.

(such as central control remote controller, etc.).

 

 

 

 

 

 

 

Terminal resistance check (connection interface SW01)

P30

Differs according to error contents of unit with

Continuation/Stop

Displayed when

Check the check code of corresponding unit by remote controller

occurrence of alarm.

(Based on a case)

error is detected

 

 

 

 

 

 

 

 

Page 84
Image 84
Toshiba RAV-SM1102CT-E Error mode detected by remote controller, Error mode detected by central remote controller