Toshiba RAV-SM563AT-E Outline of specifications, Remarks, Drain pump control, W arning

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 66
Image 66

No.

Item

 

 

Outline of specifications

Remarks

 

 

 

 

 

9

Drain pump control

1)

In cooling operation (including Dry operation), the

 

 

 

 

drain pump is usually operated.

 

 

 

2)

If the float switch operates while drain pump

 

 

 

 

operates, the compressor stops, the drain pump

 

 

 

 

continues the operation, and a check code is

 

 

 

 

output.

 

 

 

3)

If the float switch operates while drain pump stops,

 

 

 

 

the compressor stops and the drain pump oper-

 

 

 

 

ates. If the float switch keeps operating for approx.

 

 

 

 

4 minutes, a check code is output.

Check code [P10]

 

 

 

 

10

After-heat

When heating operation stops, the indoor fan oper-

 

 

elimination

ates with LOW mode for approx. 30 seconds.

 

 

 

 

 

11

Louver control

1) Louver position setup

 

 

(For 4-way air

 

When the louver position is changed, the

 

 

 

 

position moves necessarily to downward dis-

 

 

discharge cassette

 

 

 

 

 

 

charge position once to return to the set posi-

 

 

type only)

 

 

 

 

 

 

tion.

 

 

 

 

 

 

 

 

 

The louver position can be set up in the follow-

 

 

 

 

 

ing operation range.

 

In cooling/dry operation In heating/fan operation

In group twin/triple operation, the louver posi- tions can be set up collectively or individually.

2)Swing setup

The swinging position can be moved in the following operation range.

All modes

 

• In group twin/triple operation, the swinging

 

 

positions can be set up collectively or individu-

 

 

ally.

W arning :

3)

When the unit stops or when a warning is output,

A check code is displayed

 

the louver automatically moves downward.

on the remote controller,

4)

While the heating operation is ready, the louver

and the indoor unit stops.

 

automatically moves upward.

(Excluding [F08] and

 

 

[L31])

– 66 –