[P04 error]

Is high-voltage

NO

protective operation by

 

TE sensor normal?

 

YES

 

 

 

Is connection of cabling

NO

 

connector normal?

 

 

YES

 

 

 

 

 

 

Does cooling outdoor fan

NO

 

normally operate?

 

YES

 

 

 

Correct connection of cabling connector.

Check TE sensor. Defect ÆReplace

 

 

NO

 

 

 

Is connection of

 

 

Correct connection of

 

 

 

connector normal?

 

 

 

connector.

 

YES

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is fan motor normal?

 

 

Replace fan motor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

Does PMV normally operate?

YES

Do not TD and TO sensors

NO

 

 

 

Correct coming-off.

 

 

 

 

 

come off the detection part?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check TE, TC, TS sensors.

 

YES

Replace electron expansion valve.

 

 

 

 

 

 

Are characteristics of

NO

 

 

 

 

 

 

Replace TD, TO,

 

TD, TO, TC sensor resistance

 

 

 

 

 

 

 

and TC sensors.

 

values normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

* Refer to Characteristics-3 and 4.

 

 

 

 

 

 

 

 

 

 

Check charged refrigerant amount.

 

 

 

 

 

 

 

 

 

 

 

 

 

Check CDB.

 

 

Check liquid/gas valves.

 

 

 

 

 

 

 

 

 

 

Check abnormal overload.

 

 

 

 

 

Defect ÆReplace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* For RAV-SM563AT-E, SM803AT-E, replace control P.C. board.