Toshiba RAV-SM563AT-E 4, 5, Outline of test operation from the wireless remote controller

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 108
Image 108

<In case of wireless remote controller>

Procedure

 

 

 

 

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn on power of the air conditioner.

 

 

 

 

 

 

1

 

 

 

 

The operation is not accepted for 5 minutes when power has been turned on at first time after installation,

 

 

and 1 minute when power has been turned on at the next time and after. After the specified time has

 

 

passed, perform a test operation.

 

 

 

 

 

 

 

 

 

 

2

 

Push [Start/Stop] button and change the operation mode to [COOL] or [HEAT] with [Mode] button.

 

Then change the fan speed to [High] using [Fan] button.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test cooling operation

 

 

 

 

Test heating operation

3

 

 

 

 

Set temperature to [18°C] using [Temperature set]

Set temperature to [30°C] using [Temperature set]

 

 

button.

 

 

 

 

 

button.

 

 

 

 

 

 

4

 

After checking the receiving sound “Pi”, immediately

After checking the receiving sound “Pi”, immediately

 

push [Temperature set] button to set to [19°C]

 

push [Temperature set] button to set to [29°C].

 

 

 

 

5

 

After checking the receiving sound “Pi”, immediately

After checking the receiving sound “Pi”, immediately

 

push [Temperature set] button to set to [18°C].

 

push [Temperature set] button to set to [30°C].

 

 

 

 

 

 

 

 

 

 

Then repeat the procedure 4 5

4 5 .

 

 

 

 

6

 

After approx. 10 seconds, all the display lamps on the sensor part of wireless remote controller,

 

[Operation] (Green), [Timer] (Green), and [Ready] (Yellow) flash and the air conditioner starts operation.

 

 

If the lamps do not flash, repeat the procedure 2 and after.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

After the test operation, push [Start/Stop] button to stop the operation.

 

 

 

 

 

 

 

 

 

<Outline of test operation from the wireless remote controller>

 

 

Test cooling operation:

 

 

 

 

 

 

 

 

 

Start

18°C

19°C

18°C

19°C

18°C

19°C

18°C

(Test operation)

Stop

Test heating operation:

 

 

 

 

 

 

 

 

 

Start

30°C

29°C

30°C

29°C

30°C

29°C

30°C

(Test operation)

Stop

Be sure to set the air speed to [High]