Toshiba RAV-SM1102BT-E Circuit Configuration And Control Specifications, Revised Mar

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 71
Image 71

Revised : Mar. 2007

9. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS

9-1. Indoor Control Circuit

9-1-1. Indoor P.C. Board Optional Connector Specifications

Function

Connector

Pin

Specifications

Remarks

No.

No.

 

 

 

 

 

 

 

 

Option output

CN60

1

DC12V (COM)

 

 

 

 

 

 

 

 

2

Defrost output

ON during defrost operation of outdoor unit

 

 

 

 

 

 

 

3

Thermo. ON output

ON during Real thermo-ON (Comp ON)

 

 

 

 

 

 

 

4

Cooling output

ON when operation mode is in cooling system

 

 

 

 

(COOL, DRY, COOL in AUTO cooling/heating)

 

 

 

 

 

 

 

5

Heating output

ON when operation mode is in heating system

 

 

 

 

(HEAT, HEAT in AUTO cooling/heating)

 

 

 

 

 

 

 

6

Fan output

ON during indoor fan ON

 

 

 

 

(Air purifier is used/Interlock cable)

 

 

 

 

 

Outside error

CN80

1

DC12V (COM)

(When continued for 1 minute)

input

 

 

 

Check code “L30” is output and forced operation stops.

 

2

DC12V (COM)

 

 

 

 

 

 

 

 

 

 

3

Outside error input

 

 

 

 

 

 

Filter option

CN70

1

Filter/Option/Humidifier

Option error input is controlled. (Protective operation

error

 

 

setup input

for device attached to outside is displayed.)

 

 

 

 

 

 

 

2

0V

* Setting of option error input is performed from remote

 

 

 

 

controller. (DN=2A)

 

 

 

 

 

CHK

CN71

1

Check mode input

Used for operation check of indoor unit.

Operation check

 

 

 

(Communication with outdoor unit or remote controller

 

2

0V

 

 

is not performed, but the specified operation such as

DISP display

CN72

1

Display mode input

indoor fan “H” or drain pump ON is output.)

 

mode

 

 

 

 

 

2

0V

Display mode enables indoor unit and remote controller

 

 

 

 

 

 

to communicate. (When power is turned on)

EXCT demand

CN73

1

Demand input

 

 

 

 

 

 

 

 

2

0V

Forced thermo-OFF operation in indoor unit

 

 

 

 

 

9-2. Outdoor Controls

9-2-1. Print Circuit Board

P.C. Board Comparison Table for Digital Inverter

P.C. board

Part No.

Model name

RAV -SM

Model name

RAV -SP

 

 

 

 

 

 

563AT-E/803AT-E

 

1103AT-E/1403AT-E

562AT-E/802AT-E

 

1102AT-E/1402AT-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main

MCC-5009

4316V284

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

MCC-1530

4316V293

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CDB

MCC-1531

4316V283

 

 

1

 

 

 

 

 

 

 

 

 

 

4316V282

 

 

 

1

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IPDU

MCC-1438

4316V291

 

 

1

 

 

1

 

 

 

 

 

 

 

4316V278

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: Applied

– 71 –

Page 71
Image 71
Toshiba RAV-SM1102BT-E, RAV-SM1102CT-E Circuit Configuration And Control Specifications, Revised Mar, Print Circuit Board