Toshiba RAV-SM802CT-E, RAV-SM1102CT-E Heat, Outline of specifications, Remarks, A zone

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 64
Image 64

No.

Item

 

Outline of specifications

 

 

Remarks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Air speed

<HEAT>

 

 

 

 

 

 

 

 

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

(Continued)

 

Ta (˚C)

 

 

 

 

 

 

 

 

 

 

 

(-0.5) –1.0

 

L(L)

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L(H)

 

 

 

 

 

 

 

(0)

Tsh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H(H)

 

 

 

 

 

 

 

 

 

 

(+0.5) +1.0

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(+1.0) +2.0

 

(HH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HH

 

 

 

 

 

C

 

 

 

 

(+1.5)

+3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(HH)

 

 

 

 

 

B

 

 

 

 

(+2.0) +4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value in the parentheses indicates one when thermostat of the remote controller works.

Value without parentheses indicates one when thermostat of the body works.

If the air speed has been changed once, it is not changed for 1 minute. However when the air speed is exchanged, the air speed changes.

When heating operation has started, the air speed selects a upward slope, that is, the high position.

If the temperature is just on the difference boundary, the

air speed does not change.

Tc: Indoor heat exchanger

• Mode in the parentheses indicates one in automatic

sensor temperature

heating operation.

 

In Tc 60°C, the air speed increases by 1 step.

[PRE-HEAT] display

In heating operation, the mode changes to [LL] if thermo-

 

 

 

 

stat is turned off.

Tc

F5

F4

If Ta 25°C when heating operation has started and when

 

 

(˚C)

 

 

 

defrost operation has been cleared, it operates with HIGH

47

 

 

 

(H) mode or (HH) for 1 minute from when Tc has entered

 

 

 

 

in E zone of cool air discharge preventive control (Item 6).

 

 

 

In automatic cooling/heating operation, the revolution

42

 

 

 

frequency of [HH] is set larger than that in the standard

 

 

 

 

F5

 

 

cooling/heating operation. However the revolution fre-

 

 

 

 

 

 

 

quency is restricted in the automatic heating operation as

 

 

 

 

shown in the following figure.

 

 

 

6 Cool air

1) In heating operation, the indoor fan is controlled based

discharge

on the detected temperature of Tc sensor or Tcj sensor.

preventive

As shown below, the upper limit of the revolution fre-

control

quency is determined.

Tc

(˚C)

 

 

Tcj

 

HH

 

 

32

 

 

H

 

 

30

 

 

L

E zone

 

 

 

28

 

 

UL

D zone

 

 

 

26

 

 

 

 

 

20

OFF

C zone

 

 

B zone

 

16

 

 

 

A zone

 

 

 

– 64 –