Toshiba RAV-SM803UT-E, RAV-SM1102CT-E, RAV-SM1102BT-E, RAV-SM1403UT-E Indoor unit, Outdoor unit

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 35
Image 35

RAV-SM563UT-E, RAV-SM562BT-E, RAV-SM562CT-E / RAV-SP562AT-E

Outer diameter of refrigerant pipe

Gas side ØA

Liquid side ØB

 

 

12.7mm

6.4mm

 

 

 

Height difference (m)

 

 

Outdoor unit

Outdoor unit

at upper side

at lower side

 

 

30

15

 

 

Indoor unit

TCJ

sensor

Air heat exchanger

TC sensor

*The refrigerating cycle of the indoor units differs according to the models to be combined. For the refrigerating cycles of the other indoor units, refer to the corresponding Service Manuals described in the list on the cover.

Height difference

TS sensor

TD sensor

Refrigerant pipe at gas side Outer dia. Ø A

Packed valve

Outer dia. Ø A

Strainer

TO sensor

Section shape

of heat insulator

Outdoor unit

Refrigerant pipe at liquid side Outer dia. Ø B

Min. Max.

5m 50m

Packed valve

Outer dia. Ø B

Modulating (PMV) (CAM-B30YGTF-2)

Strainer

4-way valve Muffler (STF-0213Z)

Ø 25 × L210 Ø 25 × L160

TE sensor

Heat exchangerØ 8 1 row 30 stages FP1.3 flat fin

Capillary

Ø3×Ø 2× L530

 

Rotary compressor

 

 

 

 

 

 

 

 

 

(DA220A2F-20L1)

 

 

 

 

 

 

 

 

Accumulator

 

 

 

 

 

 

 

 

 

 

(1500cc)

 

 

 

 

 

 

 

R410A 1.5 kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

Heating

 

 

Pressure

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

Indoor

temp. conditions

 

 

 

(MPa)

 

 

Indoor heat

Outdoor heat

revolutions per

 

 

 

Discharge

Suction

(DB/WB) (°C)

 

 

 

fan

 

 

 

second (rps)

 

 

 

 

exchanger

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

Pd

Ps

(TD)

(TS)

(TC)

(TE)

*

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.71

1.03

75

15

10

38

43

HIGH

27/19

35/–

Cooling

Overload

3.48

1.16

81

20

16

51

44

HIGH

32/24

43/–

 

Low load

1.92

0.74

34

5

2

11

24

LOW

18/15.5

–5/–

 

Standard

2.22

0.72

32

6

38

2

41

HIGH

20/–

7/6

Heating

Overload

3.47

1.16

81

20

55

15

41

LOW

30/–

24/18

 

Low load

1.79

0.25

71

–16

30

–18

70

HIGH

15/–

–15/(70%)

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

– 35 –

Page 35
Image 35
Toshiba RAV-SM803UT-E service manual Indoor unit, Outdoor unit, RAV-SM563UT-E, RAV-SM562BT-E, RAV-SM562CT-E / RAV-SP562AT-E