Toshiba RAV-SM1402CT-E, RAV-SM1102CT-E, RAV-SM803AT-E How to set up central control address number

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 115
Image 115

6. External View of P.C. Board

Terminator (SW01)

52

85

7.Address Setup

In addition to set up the central control address, it is necessary to change the indoor unit number. (Line/Indoor/Group address).

For details, refer to TCC-LINK Adapter Installation Manual.

12-3. How to set up central control address number

When connecting the indoor unit to the central control remote controller using TCC-LINK adapter, it is neces- sary to set up the central control address number.

• The central control address number is displayed as the line No. of the central control remote controller.

1.Setup from remote controller at indoor unit side

*If you use the network adapter P.C. board, it is effective only when No. 7 of setup switch SW01 on P.C. board is turned off.

<Procedure> Perform setup while the unit stops.

1 Push TEST + VENT buttons for 4 seconds or more.

When group control is executed, first the unit No. RLL is displayed and all the indoor units in the group control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1)

(Keep RLL displayed status without pushing UNIT button.)

In case of individual remote controller which is not group-controlled, Line address and Indoor unit address are displayed.

2

Using temperature setup

TEMP.

buttons, specify item code 03.

 

3

Using timer time

TIME

buttons, select the setup data. The setup data is shown in the right

 

 

table (Table 1).

 

 

 

 

4

Push SET button. (OK if display goes on.)

 

 

 

 

 

(Fig.1)

 

• To change the item to be set up, return to Procedure 2.

5 Push TEST

button.

The status returns to usual stop status.

 

(Table 1)

 

 

Setup data

Central control address No.

 

 

0001

1

0002

2

0003

3

:

:

0064

64

 

 

0099

Unset (Setup at shipment from factory)

 

 

2

1

5

SET DATA

 

UNIT

No.

R.C.

No.

TEMP.

ON / OFF

 

TIMER SET

FAN

MODE

3

 

TIME

SWING/FIX

VENT

FILTER

 

 

 

1

RESET TEST

SET CL

UNIT

 

 

 

 

 

 

 

 

 

4

– 115 –

Page 115
Image 115
Toshiba RAV-SM1402CT-E, RAV-SM1102CT-E, RAV-SM1102BT-E, RAV-SM1403UT-E How to set up central control address number