Toshiba RAV-SM802BT-E Except 4-way Air Discharge Cassette Type and Under Ceiling Type

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 107
Image 107

(Except 4-way Air Discharge Cassette Type and Under Ceiling Type)

1 Remove a screw which fixes the serial olate of the receiver part on the wireless remote controller.

Remove the nameplate of the reciver section by inserting a minus screwdriver, etc. into the notch at the bottom of the plate, and set the Dip switch to [TEST RUN ON].

2 Execute a test operation with button on the wireless remote controller.

, and LED flash during test operation.

Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is invalid.

Do not use this method in the operation other than test operation because the equipment is damaged.

3

4

Use either [COOL] or [HEAT] operation mode for test operation.

• The outdoor unit does not operate approx. 3 minutes

 

after power-ON and operation stop.

Receiver unit

After the test operation finished, stop the air

Spacer

M4 × 25 screw

conditioner from the wireless remote controller,

(2 pieces)

and return Dip switch of the sensor section as before.

 

(A 60 minutes timer clearing function is attached to the sensor section in order to prevent a continuous test operation.)

Notch Nameplate

Small screw

(Under Ceiling Type only)

1 Turn off power of the air conditioner.

Remove the adjust corner cap attached with sensor section from the ceiling panel. For removing method, follow to the installation manual attached to the ceiling panel. (Be careful to handle the sensor section because cables are connected to the sensor section.)

Remove the sensor cover from the adjust corner cap. (1 screw)

2 Change Bit [1: TEST] of the switch [S003] on the sensor P.C. board from OFF to ON.

Mount the sensor cover and attach the adjust corner cap with with sensors to the ceiling panel.

Turn on power of the air conditioner.

3 Push button of the wireless remote controller and select an operation mode [COOL] or [HEAT] with MODE button. (All the display lamps of the wireless remote controller sensor section flash during the tst operation.)

Do not use operation mode other than [COOL] or [HEAT].

Error is detected as usual.

4

5

When the test operation has finished, push button to stop the operation.

Turn off power of the air conditioner.

Change Bit [1] of the switch [S003] on the sensor P.C. board from ON to OFF. Attach the adjust corner cap with sensors to the ceiling panel.

 

4

3

2 1

2 3 4

ON

 

 

 

 

 

– 107 –