Toshiba RAV-SM803UT-E, RAV-SM1102CT-E, RAV-SM1102BT-E Outdoor fan control, Operation with WE

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 77
Image 77

4. Outdoor fan control

Allocations of fan tap revolutions [rpm]

 

W 1

W

2 W 3

W 4

W 5 W

6 W 7

W 8

W

9 W

A

W B

W C

W D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM56

200

300

350

410

480

500

530

560

640

670

700

750

800

840

840

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM80

200

300

350

410

480

500

530

560

640

670

700

750

840

940

980

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM110

250

280

320

360

410

460

520

580

640

700

760

860

860

900

930

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM140

250

280

320

360

410

460

520

580

640

700

760

860

860

900

970

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1)Cooling fan control

Q The outdoor fan is controlled by TE, TD, and TO sensors and also revolution frequency of the opera- tion. The outdoor is controlled by every 1 tap of DC fan control (15 taps).

R Only during 60 seconds after the operation has started, the fan is fixed with the maximum fan tap which corresponds to the zone in the following table.

After then the fan is controlled by TE sensor temperature.

S Considering a case that TE sensor has come out of the holder, the fan is controlled so that revolution frequency of the fan increases regardless of TE if temperature of TD sensor has risen.

 

a

b

 

 

 

SM56, SM80

36

32

 

 

 

SM110, SM110

29

26

 

 

 

Operation with WE

TE [˚C]

TD [˚C]

 

 

+1 tap/20 seconds

85

 

 

 

 

 

 

a

 

80

 

rpm hold

Operation with

 

 

 

 

 

75

maximum tap in

b

 

each zone

–1 tap/20 seconds

 

65

Usual fan control

 

 

 

(The operation frequency differs according to the model type.)

Temp. range

Below 30Hz

Above 30 Hz below 45 Hz

Above 45 Hz

 

 

 

 

 

 

Min.

Max.

Min.

Max.

Min.

Max.

 

 

 

 

 

 

 

 

 

 

 

29°C < TO

W5

WA

W7

WC

W9

WF

15

< TO < 29°C

W3

W7

W5

W9

W7

WB

5

< TO < 15°C

W2

W5

W4

W7

W6

W9

0

< TO < 5°C

W1

W3

W3

W5

W4

W7

 

TO < 0°C

W1

W2

W2

W4

W3

W5

 

 

 

 

 

 

 

 

 

TO error

W1

WF

W1

WF

W1

WF

 

 

 

 

 

 

 

 

– 77 –