Toshiba RAV-SM1402CT-E Systematic Refrigerating Cycle Diagram, Indoor Unit/Outdoor Unit

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 31
Image 31

4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM

4-1. Indoor Unit/Outdoor Unit

RAV-SM563UT-E, RAV-SM562BT-E, RAV-SM562CT-E / RAV-SM563AT-E

Outer diameter of refrigerant pipe

Gas side ØA

Liquid side ØB

 

 

 

 

 

12.7mm

6.4mm

 

 

 

 

 

 

 

 

Height difference (m)

 

 

 

 

 

Outdoor unit

Outdoor unit

 

at upper side

at lower side

 

 

 

 

 

30

30

 

 

 

 

 

 

 

 

 

 

TC sensor

Indoor unit

Air heat exchanger

TCJ sensor

Height difference

TS sensor

2-step muffler

Ø 19 .05 × 200L

TD sensor

4-way valve (STF-0108Z)

Muffler

Ø 19 × L160

Rotary compressor

(DA150A1F-20F)

Refrigerant pipe

 

Refrigerant pipe

 

at gas side

 

at liquid side

 

Ø 12.7

Section shape

Ø 6.4

 

 

 

 

 

of heat insulator

 

 

 

 

Min.

Max.

 

 

5m

30m

Packed valve

 

Packed valve

 

Outer dia. Ø A

Outdoor unit

Outer dia. Ø B

 

 

 

 

 

 

PMV

 

 

 

(Pulse Motor Valve)

 

TO sensor

 

(CAM-B30YGTF-2)

 

 

 

 

 

 

Strainer

 

 

TE

 

 

 

sensor

 

 

Heat exchanger Ø 8 ripple, 2 rows,

14 stepsDistributor FP1.3 flat fin

 

 

 

 

 

 

 

 

 

 

 

R410A 1.0 kg

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

 

Pressure

 

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

Indoor

temp. conditions

 

 

(MPa)

(kg/cm²G)

 

 

Indoor heat

Outdoor heat

revolutions per

 

 

Discharge

Suction

(DB/WB) (°C)

 

 

fan

 

 

second (rps)

 

 

 

 

 

 

exchanger

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

*

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

3.50

0.97

35.7

9.9

85

14

12

48

70

HIGH

27/19

35/–

Cooling

Overload

3.90

1.08

39.8

11.0

93

26

17

54

70

HIGH

32/24

43/–

 

Low load

1.90

0.70

19.4

7.1

48

7

5

30

50

LOW

18/15.5

–5/–

 

Standard

2.31

0.61

13.6

6.2

87

5

40

1

97

HIGH

20/–

7/6

Heating

Overload

2.86

0.89

29.2

9.1

86

17

47

11

95

LOW

28/–

24/18

 

Low load

1.86

0.25

19.0

2.6

69

–14

31

–15

98

HIGH

15/–

–10/(70%)

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

– 31 –

Page 31
Image 31
Toshiba RAV-SM1402CT-E, RAV-SM1102CT-E Systematic Refrigerating Cycle Diagram, Indoor Unit/Outdoor Unit, Indoor unit