Toshiba RAV-SM1102CT-E, RAV-SM1102BT-E Revised Mar, P29 error, H03 error, For RAV-SM563AT-E

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 94
Image 94

Revised : Mar. 2007

[P29 error]

 

NO

 

 

 

 

Are connections of

 

 

Check and correct circuit cabling

 

 

 

 

 

cable/connector normal?

 

 

 

such as cabling to compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

NO

Is compressor normal?

YES

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

Is not earthed?

 

 

 

Compressor error ÆReplace

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is not winding shorted?

 

 

 

 

 

 

 

 

 

Compressor error ÆReplace

 

 

 

 

 

 

 

 

 

 

 

 

 

(Is resistance between windings 0.6 to 1.2W?)

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

Is not winding opened?

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor error ÆReplace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check IPDU P.C. board.

 

* For RAV-SM563AT-E,

SM803AT-E,

 

 

 

 

 

Defect ÆReplace

 

replace control P.C.

board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[H03 error]

Are cablings of power and

current sensor normal?

YES

Check IPDU.

Defect ÆReplace

NO

Check and correct circuit cables.

* For RAV-SM563AT-E, SM803AT-E, replace control P.C. board.

– 94 –

Page 94
Image 94
Toshiba RAV-SM1102CT-E, RAV-SM1102BT-E, RAV-SM1403UT-E service manual Revised Mar, P29 error, H03 error, For RAV-SM563AT-E