Toshiba RAV-SM1402CT-E Revised Mar, E04 error, Are 1, 2, 3 inter-unit cables normal?

Models: RAV-SP1102UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM563AT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM803UT-E RAV-SM803AT-E RAV-SM1402BT-E RAV-SM1103UT-E RAV-SM1402CT-E RAV-SM1403UT-E RAV-SM1102BT-E RAV-SM1102CT-E

1 195
Download 195 pages 37.15 Kb
Page 87
Image 87

[E04 error]

NO

Does outdoor unit operate?

YES

NO

Is setup of group address correct?

YES

Are 1, 2, 3 inter-unit cables normal?

NO

 

 

 

YES

 

 

 

 

 

 

Are connections from connectors

NO

of inter-terminal blocks (1, 2, 3)

 

 

of indoor/outdoor units normal?

 

 

YES

 

 

 

 

 

 

Revised : Mar. 2007

Check item code [14].

Correct inter-unit cable.

Correct connection of connector.

 

 

 

 

 

 

Does voltage between

NO

 

 

Check indoor P.C. board

 

2 and 3 of inter-terminal blocks (1, 2, 3)

 

 

 

(MCC-1402).

 

 

of indoor unit vary?*

 

 

 

Defect ÆReplace

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

*As shown in the following figure, perform measurement within 20 seconds after power ON.

S5277G

Black

3

White

2

1

Inter-terminal block

YES

Does case thermo. operate?

NO

Check/Correct charged refrigerant amount.

Check indoor P.C. board (MCC-1402).

Defect ÆReplace

MCC-5009

Check outdoor P.C. board Defect ÆReplace

MCC-1531 and MCC-1438

RAV-SM563AT-E

RAV-SM803AT-E

RAV-SM1103AT-E

RAV-SM1403AT-E

RAV-SP562AT-E RAV-SP802AT-E RAV-SP1102AT-E RAV-SP1402AT-E