Chapter 8 High-speed counter, PWM / Pulse train output and Analogue I/O

8.1.4 Input/Output Setting (Mode 10)

Mode 10 had been added since Ver. 01.13. I/O assignment of mode 10 is very flexible as follows.

Parameter setting is compatible with existing mode 0 to 3 except for WRF071. Operation of FUN command (FUN 140 - 150) is same for all the mode 0 to 10.

„Outline

Input and output are configured in every group as below.

X0 X1

Y100

Group 1

„Mode setting

X2

X3

X4

X5

Y101 Y102

Group 2 Group 3

Fig. 8.4 Group of mode 10

X6 X7

Y103

Group 4

Set "H10" to the special internal output WRF070.

„In/output setting

Set parameter according to the following table to the special internal output WRF071.

Bit :

WRF071 :

Default :

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

 

 

 

 

 

 

 

 

 

 

 

 

 

Group 1

 

 

Group 2

 

 

Group 3

 

 

Group 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

 

 

 

 

Fig. 8.5 Bit table of WRF071

 

 

 

 

 

 

Select one of below combinations and set in WRF071 for every group.

Fig. 8.2 Parameter for in/output setting

Parameter

X0 / 2 / 4 / 6

X1 / 3 / 5 / 7

Y100/101/102/103

H 0

Standard input

Standard input

Standard output

H 1

 

 

PWM output

H 2

 

 

Pulse output

H 3

 

Interrupt input

Standard output

H 4

 

 

PWM output

H 5

 

 

Pulse output

H 6

Counter input

Standard input

Standard output

H 7

 

 

Counter output

H 8

 

Preload input

Standard output

H 9

 

 

Counter output

H A

 

Strobe input

Standard output

H B

 

 

Counter output

Others

Standard input

Standard input

Standard output

Since 10 points type does not have input X6 and X7, possible value for group 4 is 0 to 2.

„ Example

Group

 

 

 

Function

 

 

Value

1

X0

: Standard input

X1

: Standard input

Y100

: Pulse output 1

Î H2

2

X2

: Counter 2

X3 :Preload input 2

Y101 : Standard output

Î H8

3

X4

: Counter 3

X5

: Standard input

Y102

: Counter output 3

Î H7

4

X6

: Standard input

X7

: Interrupt input 4

Y103

: Standard output

Î H3

Î WRF071 = H2873

8-4

Page 213
Image 213