Note: See Chapter 7, “Parts listing, Type 8839,” on page 105 to determine which components should be replaced by a field service technician.

Power problems

Symptom

FRU/action

 

 

 

Power switch does not work

1.

Reseat connector.

and reset button, if

2. Front bezel with customer card.

supported, does work.

3.

System board.

 

 

 

 

The blade server does not

1.

Make sure that:

turn on.

 

a. The power LED on the front of the BladeCenter unit is on.

 

 

 

 

b. The LEDs on all the BladeCenter power modules are on.

 

 

c. If the blade server or attached storage expansion unit is in blade bay 7-14,

 

 

power modules are in power bays 1, 2, 3 and 4.

 

 

d. The power-on LED on the blade server control panel is blinking slowly.

 

 

v If the power LED is blinking rapidly and continues to do so, the blade

 

 

server is not communicating with the management module; reseat the

 

 

blade server, then go to step 3

 

 

v If the power LED is off, the blade bay is not receiving power, the blade

 

 

server is defective, or the LED information panel is loose or defective.

 

 

e. Local power control for the blade server is enabled (use the BladeCenter

 

 

management module Web interface to verify), or the blade server was

 

 

instructed through the management module (Web interface or IBM Director)

 

 

to turn on.

 

2. If you just installed an option in the blade server, remove it, and restart the

 

 

blade server. If the blade server= now turns on, you might have installed more

 

 

options than the power to that blade bay supports.

 

3. Try another blade server in the blade bay; if it works, replace the faulty blade

 

 

server.

 

4. See “Undetermined problems” on page 101.

 

 

The blade server does not

The microprocessor with the lowest feature set must be used as the startup

turn on and the following

microprocessor (microprocessor 1; see “Processor board components” on

conditions are present:

page 35). Move the microprocessor in location U66 to location U70, and move the

1. The amber system error

microprocessor in location U70 to location U66.

 

 

LED on the Blade Center

 

 

unit system LED panel is lit;

 

 

2. The amber blade error LED

 

 

on the blade server LED

 

 

panel is lit; and

 

 

3. The system error log

 

 

contains the message

 

 

CPUs mismatched.

 

 

 

 

 

The blade server turns off for

1. Make sure that all blade bays have a blade server, expansion unit, or filler

no apparent reason

 

blade properly installed. If these components are missing or improperly

 

 

 

 

installed, an over-temperature condition may result in shutdown.

 

2. If microprocessor LED is illuminated, replace the microprocessor.

 

 

 

The blade server does not

1. Determine whether you are using an ACPI or non-ACPI operating system.

turn off.

 

If you are using a non-ACPI operating system:

 

 

 

 

a. Press Ctrl+Alt+Delete.

 

 

b. Turn off the system by holding the power-control button for 4 seconds.

 

 

c. If computer fails during BIOS POST and power-control button does not

 

 

work, remove the blade server from the bay and reseat it.

 

2. If the problem remains or if you are using an ACPI-aware operating system,

 

 

suspect the system board.

 

 

 

94BladeCenter HS40 Type 8839: Hardware Maintenance Manual and Troubleshooting Guide