Juniper Networks SRX 210 manual Clearance Requirements for the Services Gateway

Models: SRX 210

1 200
Download 200 pages 27.83 Kb
Page 74
Image 74
Table 23: Clearance Requirements for the Services Gateway

SRX210 Services Gateway Hardware Guide

Clearance Requirements for Airflow and Hardware Maintenance of the SRX210 Services Gateway

When planning the installation site for the SRX210 Services Gateway, you need to allow sufficient clearance around the rack or cabinet where you are planning to install the device.

When planning the installation site for the services gateway, consider the following:

For the cooling system to function properly, the airflow around the chassis must be unrestricted.

For service personnel to remove and install hardware components, there must be adequate space at the front and back of the device. Allow at least 24 in. (61 cm) both in front of and behind the device.

If you are mounting the device in a rack with other equipment, or if you are placing it on the desktop near other equipment, ensure that the exhaust from other equipment does not blow into the intake vents of the chassis.

Table 23 on page 54 provides information on the clearance requirements for maintaining the optimum airflow and the distances for facilitating easy maintenance of the device.

Table 23: Clearance Requirements for the Services Gateway

 

Recommended

 

Location

Clearance

Requirement for Clearance

Front of the chassis

2.5 in. (6.35 cm)

Space for service personnel to

 

 

remove and install hardware

 

 

components

 

 

NOTE: More space is required for

 

 

installing and removing Mini-PIMs.

Rear of the chassis

2.5 in. (6.35 cm)

Space for service personnel to

 

 

remove and install hardware

 

 

components

Between front-mounting flange

2.5 in. (6.35 cm)

Space for cable management and

and rack or cabinet edge

 

organization

Between side of the chassis and

2.5 in. (6.35 cm)

Space for the cooling system to

any non-heat-producing surface

 

function properly and to maintain

such as a wall or cabinet side

 

unrestricted airflow around the

 

 

chassis

Between side of the chassis and

2.5 in. (6.35 cm)

Space for the cooling system to

devices that have fans or

 

function properly and to maintain

blowers

 

unrestricted airflow around the

 

 

chassis

54Clearance Requirements for Airflow and Hardware Maintenance of the SRX210 Services Gateway

Page 74
Image 74
Juniper Networks SRX 210 manual Clearance Requirements for the Services Gateway